Gree GMV6 DC Inverter VRF Units Service Manual
170
"P8" IPM Over Temperature
Protection for the
Compressor Drive Board
Whether over-temperature
protection of IPM module is triggered
upon power-on?
The compressor drive board
operates improperly
No
Replace the compressor drive
board
Yes
Check whether the screws are
tightened and whether the IPM
module is coated with thermal
grease
No
2.133 "P9" Loss of Synchronization Protection for Inverter
Compressor
Fault display:
main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is P9, it
indicates the loss of synchronization protection for the inverter compressor.
Possible causes:
■ The compressor drive board operates improperly.
■ The compressor is damaged.
Troubleshooting: