Multi Variable Air Conditioners Indoor Unit for North America
100
Pipe Diameter
(
mm/in.
)
Tightening Torque
6(1/4)
15-30N·m(11-22ft.-1b.)
9.5(3/8)
35-40N·m(26-29ft.-1b.)
12.7(1/2)
45-50N·m(33-37ft.-1b.)
16(5/8)
60-65N·m(44-48ft.-1b.)
5 Installation of Drain Pipe
5.1 Precautions When Doing the Piping Work
◆
Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that
air may not remain trapped inside the pipe.
For example:
◆
Keep pipe size equal to or greater than that of the connecting pipe.
◆
Install the drain piping as shown and take measures against condensation. Improperly rigged
piping could lead to leaks and eventually wet furniture and belongings.
◆
When directly connecting a hard vinyl chloride pipe joint to the drain hose connected to the indoor
unit, use a commercially available hard vinyl chloride pipe joint (nominal diameter 13mm).
◆
Drain hose connectedto the indoor unitCommercially availablehard vinyl chloride pipejoint
(nominal diameter 13mm)Commercially availablehard vinyl chloride pipe(nominal diameter 13mm)
◆
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in
the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger.
Summary of Contents for GMV-N07G/A3A-D(U)
Page 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Page 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Page 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Page 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Page 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...