Multi Variable Air Conditioners Indoor Unit for North America
48
parameter value settings. The parameter value blinks. Adjust the parameter value by pressing ― ‖ or ― ‖
and then press the ―ENTER/CANCEL‖ button to complete settings.
(3)
Press the ―ENTER/CANCEL‖ button to return to the upper-level menu till quitting parameter
settings.
The user parameter setting list is as follows:
Table 4.2 User Parameter Setting List
Parameter
Code
Parameter
Name
Parameter Range
Default
Value
Remark
P10
Master IDU
settings
00: does not change the
master/slave status of
the current IDU
01: sets the current IDU
to master IDU
00
After the IDU connected
with the current wired controller is
successfully set to master IDU, "MASTER"
on the wired controller is on.
P11
Infrared
connection
settings of
wired controller
00: disabled
01: enabled
01
This setting can only be enabled through
the master wired controller.
When the infrared remote receiving
function of the wired controller is disabled,
neither the master nor slave wired
controller can receive remote signals. The
wired controllers can only be operated by
pressing.
P13
Wired
controller
address
settings
01: master wired
controller
02: slave wired
controller
01
When two wired controllers simultaneously
control one or more IDUs, the two wired
controllers should use different addresses.
The slave wired controller (address: 02)
does not have the unit parameter setting
function except its own address settings.
P14
One wired
controller
controls
multiple IDUs
quantity
settings
00: disabled
01-16: number of indoor
units
01
This value is set based on the number of
connected IDUs.
If the current value is inconsistent with the
actual number of group-controlled IDUs, an
―L9‖ fault may occur.
P30
Static pressure
settings for
indoor fan
Type 1: 03.04.05.06.07
Type 2:
01.02.03.04.05.06.07.08
.09
05
After identifying the IDU type, the wired
controller only displays the available static
pressure levels.
①
. The static pressure levels fall into five
levels and nine levels for VRF IDUs.
Wired controller can be adapted to the
different types of indoor units that it
possesses 1-9 level selection for
setting static pressure.If the static
pressure levels received by the IDU
from the wired controller, remote
controller, or remote monitoring
system exceed the setting range, the
limit value prevails.
②
. During power-on and synchronization,
the setting value of static pressure
levels is determined by settings of the
IDU.
P31
High-ceiling
installation
00: standard-ceiling
installation height
01: high-ceiling
installation height
00
Only applicable to cassette units
P33
Timer function
settings
00: count down timing
01: time-point timing
00
P34
Repeating
validity for
time-point
timing
00: single timing
01: repeated everyday
00
This setting is valid only when the timer
function is set to time-point timing.
P37
Cooling setting
17°C -30°C
25
Cooling setting temperature
– heating
Summary of Contents for GMV-N07G/A3A-D(U)
Page 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Page 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Page 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Page 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Page 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...