Multi Variable Air Conditioners Indoor Unit for North America
65
04
Module 4
C11
Indoor unit quantity query in one-to-many control mode
C12
Temperature query for outdoor environment temperature sensor
C13
CAN2 bus line ID query
C14
Inlet-tube temperature query of IDU
C15
Outlet temperature query of IDU
C16
Opening degrees query of electronic expansion valve of IDU
n2
Capacity configuration ratio upper-limit query of outdoor and IDUs
n4
Highest capacity output limitation query
n6
Historical fault query ingress of ODU
01
Fault 1
02
Fault 2
03
Fault 3
04
Fault 4
05
Fault 5
A6
Unit cooling/heating function
A7
Outdoor silent mode
4.4.3 Parameter Settings
For parameter settings, users can set user parameters and engineering parameters of the unit. The
parameter setting method is as follows:
(1) After entering parameter query, switch the query code to "C00". Press and hold "
CLOCK
" for five
seconds to enter the parameter setting status. The setting text is displayed and "P00" blinks in the
temperature area.
(2) Press "
" to switch the setting code and select a unit parameter to be set (see Table 2.6 for
parameters that can be set).
(3) Press "
TEMP
" to enter parameter settings. The current parameter value blinks in the timer
area. Press "
" to change the parameter value.
(4) Press "
TEMP
" to confirm query and return to step 2.
After entering engineering commissioning, the system automatically quits the engineering
commissioning status if no valid operations are performed within 20 seconds. To directly quit the
engineering commissioning status, press "
CLOCK
".
Table 2.6 Setting Parameters
Setting
Code
Setting Content
Setting Value
P00
Invalid
P10
Master IDU settings
00: not changing the current settings
01: setting the corresponding IDU to master IDU
001-255: setting the IDU corresponding to *** to master IDU
P15
Power-down memory mode
settings
00: standby after power-down recovery
01: restoring the original status after power-down recovery
P17
Historical fault clearing
00: not cleared
01: cleared
P20
Indoor environment temperature
value
01: temperature sensor of air return vent
02: temperature sensor of wired controller
03: temperature sensor of air return vent for cooling, dehumidifying,
and air supply; temperature sensor of wired controller for heating
04:
temperature
sensor
of
wired
controller
for
cooling,
dehumidifying, and air supply; temperature sensor of air return vent
for heating and automatic mode
Summary of Contents for GMV-N07G/A3A-D(U)
Page 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Page 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Page 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Page 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Page 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...