Multi Variable Air Conditioners Indoor Unit for North America
22
Air Filter
PP
PP
PP
PP
Insulation Material
Foamed polystyrene
Refrigeration Control Device
EXV
EXV
EXV
EXV
Protection Device
Fuse
Fuse
Fuse
Fuse
4.8 Fresh air Processing Type Indoor Unit
Model
GMV-NDX72P/A-T(U)
GMV-NDX96P/A-T(U)
Product Code
CM810N0480
CM810N0470
Cooling Capacity
Btu/h
72000
96000
kW
21.1
28.1
Heating Capacity*1
Btu/h
55000
68000
kW
16.1
20.0
Heating Capacity*2
Btu/h
68000
75000
kW
20.0
22.0
Casing Finish
Galvanized Steel plate
Dimensi
ons(W×
D×H
)
Outline
mm
1483×791×385
1483×791×385
in.
58-3/8×31-1/8×15-3/16
58-3/8×31-1/8×15-3/16
Packaging
mm
1578×883×472
1578×883×472
in.
62-1/8×34-3/4×18-9/16
62-1/8×34-3/4×18-9/16
Net Weight
lbs.
181
181
kg
82
82
Gross Weight
lbs.
229
229
kg
104
104
Pipe
Connecti
on
Liquid Side
mm
Φ9.52
Φ9.52
in.
Φ3/8
Φ3/8
Gas Side
mm
Φ19.05
Φ22.2
in.
Φ3/4
Φ7/8
Drain Pipe
mm
Φ30
Φ30
in.
Φ1-1/4
Φ1-1/4
Power Supply
1-phase 208/230V 60Hz
Fan
Type * Quantity
Centrifugal*2
Centrifugal*2
Driving Mechanism
Direct-driven
Motor Type
BLDC
Motor Power
Input
W
760
860
Motor
Running
Current
A
4.3
4.9
Airflow
Rate(H/M/L)
CFM
1180/880~1765
1470/1180~2060
m
3
/h
2000/1500~3000
2500/2000~3500
Exter
nal
Static
Press
ure
Defa
ult
in.W.
G
0.80
0.80
Pa
200
200
Rang
e
in.W.
G
0.20~1.20
0.20~1.20
Pa
50~300
50~300
Sound Pressure
Level(H/M/L)
dB(A)
45~54
47~54
Heat Exchanger
/
Air Filter
PP
Insulation Material
Foamed polystyrene
Refrigeration Control Device
EXV
Protection Device
Fuse
Summary of Contents for GMV-N07G/A3A-D(U)
Page 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Page 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Page 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Page 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Page 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...