Multi Variable Air Conditioners Indoor Unit for North America
134
4.11 Air Handler type Indoor Unit
Motor and fan
Precondition: The power supply has been disconnected.
Procedures
Diagrams
Operating Instructions
1. Remove the upper
panel.
● Loosen screws round the upper
panel with a screwdriver.
● Remove the upper panel from
unit.
2. Remove the fan.
● Disconnect the wires of the fan
from the wiring terminal and draw
them out.
● Loosen screws located at the
front of the fan with a screwdriver.
● Remove the fan from the unit.
3. Remove the motor.
● Loosen screws fixing the motor
and fan blades.
● Loosen screw bolts fixing the
bracket.
● Remove the motor rightward
from the fan.
4. Reinstall the fan.
● Place the motor at the proper
position.
● Tighten screws fixing the motor
and fan blades.
● Tighten screw bolts fixning the
motor bracket.
● After the installation,
reassemble the unit as before.