Multi Variable Air Conditioners Indoor Unit for North America
95
Unit: mm
(
in.
)
MODEL
DIMENSION
W
D
H
A
B
GMV-ND24A/A-T(U)
460
(
18-1/8
)
540
(
21-1/4
)
1105
(
43-1/2
)
295
(
11-5/8
)
426
(
16-3/4
)
GMV-ND30A/A-T(U)
460
(
18-1/8
)
540
(
21-1/4
)
1105
(
43-1/2
)
295
(
11-5/8
)
426
(
16-3/4
)
GMV-ND36A/A-T(U)
540
(
21-1/4
)
540
(
21-1/4
)
1224
(
48-1/4
)
295
(
11-5/8
)
508
(
20
)
GMV-ND42A/A-T(U)
540
(
21-1/4
)
540
(
21-1/4
)
1224
(
48-1/4
)
295
(
11-5/8
)
508
(
20
)
GMV-ND48A/A-T(U)
630
(
24-7/8
)
540
(
21-1/4
)
1224
(
48-1/4
)
295
(
11-5/8
)
508
(
20
)
GMV-ND54A/A-T(U)
630
(
24-7/8
)
540
(
21-1/4
)
1224
(
48-1/4
)
295
(
11-5/8
)
508
(
20
)
3.11.2 Installation notice
When installing the air handler, take consideration to minimize the length of refrigerant tubing as
much as possible. Do not install the air handler in a location either above or below the condenser that
violates the instructions provided with the condenser. Service clearance is to take precedence. Allow a
minimum of 24‖ in front of the unit for service clearance. When installing in an area directly over a
finished ceiling (such as an attic), an emergency drain pan is required directly under the unit. See local
and state codes for requirements. When installing this unit in an area that may become wet, elevate the
unit with a sturdy, non-porous material. In installations that may lead to physical damage (i.e. a garage) it
is advised to install a protective barrier to prevent such damage.
This air handler is designed for a complete supply and return ductwork system. Do not operate this
product without all ductwork attached.
Based upon the actual conditions, if air handler is installed as type (A), the air handler should be
concealed in a specific room or space and make sure the air handler is not accessible to the general
public.
Based upon the actual conditions, if air handler is installed as type (B), make sure that there is
enough space for care and maintenance and the height between the air handler and ground is above
2500mm. And the air handler is not accessible to the general public.
Summary of Contents for GMV-N07G/A3A-D(U)
Page 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Page 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Page 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Page 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Page 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...