Multi Variable Air Conditioners Indoor Unit for North America
77
3.2.3 Selection of Air Switch and Power Cord
Model
Power Cord Size
Air Switch apacity
(A)
Minimum Sectional
Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power
Cord
(mm
2
/AWG)
GMV-ND07T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND09T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND12T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND15T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND18T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND24T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND30T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND36T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND42T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-ND48T/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
3.3 Installation of Wall-mounted Indoor Unit
3.3.1 Outline and Installation Dimension
Unit:
mm (in.)
Model
W
H
D
GMV-N07G/A3A-D(U)
GMV-N09G/A3A-D(U)
843
(33-1/5)
275
(10-5/6)
180
(7)
GMV-N12G/A3A-D(U)
GMV-N18G/A3A-D(U)
940
(37)
298
(11-3/4)
200
(7-7/8)
GMV-N24G/A3A-D(U)
1008
(39-2/3)
319
(12-5/9)
221
(8-5/7)
Summary of Contents for GMV-N07G/A3A-D(U)
Page 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Page 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Page 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Page 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Page 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...