Multi Variable Air Conditioners Indoor Unit for North America
121
5. Remove the
electrical box
cover 1
●Press on the buckle of the box cover
1 and then take off the cover.
6. Remove the
main board
●Release the wiring terminals
connected to the main board.
●Remove the main board.
7. Remove the
electrical box
●Unscrew the screws fixing the
electrical box with a screwdriver.
●Remove the electrical box.
8. Remove the
evaporator
●Use a screwdriver to unscrew the
screws fixing the press plate of
connection pipe on the back of the unit
and take off the press plate.
●Unscrew the screws of evaporator
with a screwdriver and then remove
the evaporator.
9.Remove motor‘s
pressing plate
●Unscrew the fixing screws of the
pressing plate with a screwdriver and
then remove it.
10. Remove the
motor and fan
●Take off the motor and fan directly.
●Use a screwdriver to unscrew the
screws connecting the motor and the
fan.
11. Install a new
motor.
●Assemble units based on the reverse
order of this procedure and power on
the units for test.