GMV DC Inverter VRF
42
(3) When the total amount of refrigerant in the system is more than the maximum amount of
refrigerant, the cooling system should be designed again. In this case, the cooling system
can also be separated into several cooling systems with small capacity, or add
corresponding ventilation measures or alarming display.
Fig. 3.6.6
①
Flow direction for refrigerant leakage.
②
Room for refrigerant leakage. Since the concentration of refrigerant is greater than that of air,
pay attention to the spaces where the refrigerant may residue, for example, the basement.
3.8 Electrical Installation
3.8.1 Notices for Electrical Installation
(1) Wiring should conform to national rules. All the parts, materials, electric work should be in
accordance with local codes.
(2) The special power supply for the air conditioning unit must be used, and the power supply
specification must be the same as the rated power supply of the unit.
(3) Power cord should be fixed soundly and reliable. Never forcibly pull the power cord.
(4) Wire size of power cord should be large enough. The damaged power cord and connecting
wire should be replaced by exclusive cable.
(5) All the electrical work should be performed by professional personnel as per local law,
regulation and this manual.
(6) The unit must be grounded reliably and it should comply with the relevant requirements of
the local country.
(7) A circuit breaker and a leakage switch that can cut off the power of the entire system must
be installed (a single unit must be equipped with a 30 mA leakage switch).
(8) Circuit breaker should have both magnetic trip and thermal trip functions so as to protect the
unit when short-circuit and overload happens. D-type breaker is advised to be used.
(9) As for wiring on site, please refer to the wiring diagram attached on the unit.
(10) Wiring between indoor and outdoor units must be properly connected by using the specified
wires, and the terminals should not be directly affected by external forces. Poor connection
or fixing may cause a fire accident.
(11) No connection is allowed in the middle of the wire. When the length of the connection wire is
not enough, please contact the designated service store to re-equip a dedicated wire with
sufficient length.