Setup
24
313875J
e.
Connect the flow meter cable.
7. Connect 1/2 in. NPT female air
supply to air inlet.
8.
Connect electrical cord.
Electrical Cord Requirements
NOTE:
Power cord is not supplied. See the following
table.
† Residual Current Device (RCD) must be rated at
300 mA if installed.
Electrical Cord Wires by Model
230V, 3 phase:
L1, L2, L3, GND
400V, 3 phase:
L1, L2, L3, N, GND
Electrical Requirements
on page 4 for detailed electrical require-
ments information.
a.
Use 5/32 in. or 4 mm hex allen wrench to con-
nect the power leads to L1, L2, L3, and N as
applicable.
b.
Connect green wire to ground (GND).
NOTICE
To prevent machine damage, supplied air must be
dried and filtered.
Installing this equipment requires access to parts
which may cause electric shock or other serious injury
if work is not performed properly. Have a qualified
electrician connect power and ground to main power
switch terminals. All electrical wiring must be done by
a qualified electrician and comply with all local codes
and regulations.
B (Blue) Side
A (Red) Side
ti17708a
Table 1: Power Cord Requirements
Model
Cord Requirements
AWG (mm
2
)
230V, 3 phase
8 (8.4), 3 wire + ground
400V, 3 phase
6 (13.3), 4 wire + ground †
F
IG
. 12: 400V, 3 phase shown
r_24C686_313998_1a
L1
L2
L3
N
GND