Troubleshooting
313875J
55
Acceptable Size and Duration of Power Line Voltage Fluctuations
The Motor Control Module is designed to withstand volt-
age fluctuations from the incoming power supply. If the
incoming power supply goes outside of the tolerable
range, an over-voltage condition is flagged and the sys-
tem shuts down in an alarm state. Excessive or
repeated over-voltage may permanently damage hard-
ware. The chart below shows the permissible magnitude
and duration of temporary over-voltage events. Consult
a qualified electrician if there are any concerns about
the available power supply.
Maximum Permissible Transient Voltage Surges
* Constructed from ITIC 1996 curve, referenced by IEC 61000-2-4
1200Vac, 1697Vdc
264Vac, 373Vdc
336Vac, 475Vdc
288Vac, 407Vdc
480Vac, 679Vdc
<--1 MW Max Surge Power
<--150 KW Max Surge Power
<--50 KW Max Surge Power
<--No Power Limit
0
200
400
600
800
1000
1200
1400
Time (seconds)
Voltage (Volts RMS)
0.000001 0.00001 0.0001 0.001 0.01
0.1
1
10