Power Line Voltage Surges
Power conversion equipment can be sensitive to voltage
fluctuations on incoming power. The Motor Control Mod-
ule falls under the category of power conversion equip-
ment because energy is stored on a capacitive bus and
then modulated to control a brushless motor. Engi-
neered design takes this into account and withstands a
wide range of conditions, but it is possible for supplied
power to occasionally fall outside the tolerable range in
industrial plants with high-amperage reactive pulsed
loads such as welding equipment. If the tolerable range
is exceeded, an overvoltage condition is flagged and the
system will shut down in an alarm state to protect itself
and alert the user of unstable power. Excessive or
repeated overvoltage may permanently damage hard-
ware.
The MAX-HOLD feature on a multimeter can be used to
determine peak DC voltage on the line. DC is the proper
setting, as opposed to AC, because peak voltage is the
critical parameter that affects the DC voltage level
stored on the capacitive bus in power conversion equip-
ment. Reading should not regularly exceed approxi-
mately 400VDC to avoid tripping the 420VDC alarm
level in the Motor Control Module. If power quality is sus-
pect, power conditioning or isolation of the device(s)
causing poor power quality is recommended. Consult a
qualified electrician if there are any concerns about the
available power supply.
Power Line Test Steps with Multimeter
i.
Set multimeter to “DC voltage”.
ii.
Connect multimeter probes to supplied power line.
iii. Press “Min Max” successively to show the peak
positive and negative DC voltages.
iv. Confirm readings do not exceed 400VDC (Motor
Control Module alarm issued at 420VDC).
The chart below shows the permissible magnitude and
duration of temporary over-voltage events:
9.
Ground the system.
a.
VPM:
grounded through power cord. See Con-
nect Electrical Cord, step #8 on page 24.
b.
Dispense Valve
: follow your local code.
c.
Fluid supply containers
: follow your local code.
d.
Dispensing target/container
: follow your local
code.
e.
To maintain grounding continuity when flushing
or relieving pressure,
hold grounded
metal
pail
firmly to a metal part of dispense valve then ini-
tiate a dispense.
10.Check hydraulic fluid levels.
The hydraulic reservoirs are filled at the factory. See
on page 87 for hydraulic fluid specifica-
tions.
This equipment must be grounded.
Maximum Permissible Transient Voltage Surges
* Constructed from ITIC 1996 curve, referenced by IEC 61000-2-4
1200Vac, 1697Vdc
264Vac, 373Vdc
336Vac, 475Vdc
288Vac, 407Vdc
480Vac, 679Vdc
<--1 MW Max Surge Power
<--150 KW Max Surge Power
<--50 KW Max Surge Power
<--No Power Limit
0
200
400
600
800
1000
1200
1400
Time (seconds)
Voltage (Volts RMS)
0.000001 0.00001 0.0001 0.001 0.01
0.1
1
10
Summary of Contents for VPM 12
Page 9: ...A Red and B Blue Components 313875J 9...
Page 50: ...Maintenance 50 313875J...