24
2581 FlowtraMag
®
Meter
Troubleshooting
Symptom
Possible Cause
Solution
No LED Lights
Unit is not powered or the power wiring
is reversed.
Check power wiring, voltage should be
12 to 32 VDC at 24W.
Solid Blue
There is no
fl
ow. If user expects to see
fl
ow, the Low Flow Cuto
ff
value may be
set too high.
Change the Low Flow Cuto
ff
value in user menu
using GF Con
fi
guration Bluetooth
®
Tool or
0252 Con
fi
guration Tool.
Solid Purple
Partially
fi
lled pipe. Flow rate is zero.
User should be aware that the pipe could be
fi
lled
> 50% and water in the pipe is stagnant or the water is
below 50% and water could be stagnant or moving.
Blinking Red
Flow measurement is out of range.
If error persists, the LED will become
solid RED after one minute.
The spiking of the
fl
ow outside the normal range could
be caused by excessive EMI or water splattering
through a partially
fi
lled pipe and creating
fl
ow spikes.
The spiking will end once the disturbance is not
present anymore.
Frequency
output does not
work
1.
Bluetooth selection is S
3
L.
2. Improper
wiring.
1. Select frequency from GF Con
fi
g Tool or
0252 Con
fi
guration Tool.
2.
Check wiring. Use the wiring diagram picture in
the 2581 FlowtraMag manual.
Frequency,
Digital or
Current Output
is Erratic
1. Electrical Noise interference with the
fl
ow measurement.
2.
Possible air pockets traveling
through the piping system.
3.
Pipe is not full and water
fl
ow creates splashing of
the electrodes.
4. Excess turbulence in
fl
uid
fl
ow pro
fi
le.
1. Verify the grounding of the 2581 FlowtraMag and
of the nearby VFDs and Pumps. If possible, use
grounding rings or connect metal portions of the
piping to closest ground.
2. Check the piping and use vents if possible,
otherwise wait for the air pockets to be eliminated
through the system.
3. Try to keep the pipe full, by installing vertical.
4. Follow product manual recommended xD
installation distances.
Output is not
Zero when
fl
ow
is stopped
1. Low Flow Cuto
ff
fl
ow value is lower
than the zero
fl
ow noise level.
2. Electrical noise is interfering with
the measurement.
3. Defective 2581 FlowtraMag.
1. Adjust the Low Flow Cuto
ff
value to be above
the noise level.
2. Verify/Modify
Grounding.
3. Contact
Technical
Support.
Forgotten
password
Forgotten/lost password
Connect blue wire to white wire while unit is powered
(for 2 to 5 seconds.) Password will reset to factory
original (last 6 digits of serial number.)