background image

24

2581 FlowtraMag

®

 Meter 

Troubleshooting

Symptom

Possible Cause

Solution

No LED Lights

Unit is not powered or the power wiring 
is reversed.

Check power wiring, voltage should be 
12 to 32 VDC at 24W.

Solid Blue

There is no 

fl

 ow.  If user expects to see 

fl

 ow, the Low Flow Cuto

  value may be 

set too high.

Change the Low Flow Cuto

  value in user menu 

using GF Con

fi

 guration Bluetooth

®

 Tool or 

0252 Con

fi

 guration Tool.

Solid Purple

Partially 

fi

 lled pipe.  Flow rate is zero.

User should be aware that the pipe could be 

fi

 lled 

> 50% and water in the pipe is stagnant or the water is 
below 50% and water could be stagnant or moving.

Blinking Red

Flow measurement is out of range.
If error persists, the LED will become 
solid RED after one minute.

The spiking of the 

fl

 ow outside the normal range could 

be caused by excessive EMI or water splattering 
through a partially 

fi

 lled pipe and creating 

fl

 ow spikes. 

The spiking will end once the disturbance is not 
present anymore.

Frequency 
output does not 
work

1.  

Bluetooth selection is S

3

L.

2. Improper 

wiring.

1.  Select frequency from GF Con

fi

 g Tool or 

0252 Con

fi

 guration Tool.

2.  

Check wiring.  Use the wiring diagram picture in 
the 2581 FlowtraMag manual.

Frequency, 
Digital or 
Current Output 
is Erratic

1.  Electrical Noise interference with the 

fl

 ow measurement. 

2.  

Possible air pockets traveling 
through the piping system. 

3.  

Pipe is not full and water 

fl

 ow creates splashing of 

the electrodes.

4.  Excess turbulence in 

fl

 uid 

fl

 ow pro

fi

 le.

1.  Verify the grounding of the 2581 FlowtraMag and 

of the nearby VFDs and Pumps.  If possible, use 
grounding rings or connect metal portions of the 
piping to closest ground.

2.  Check the piping and use vents if possible, 

otherwise wait for the air pockets to be eliminated 
through the system.

3.  Try to keep the pipe full, by installing vertical.
4.  Follow product manual recommended xD 

installation distances.

Output is not 
Zero when 

fl

 ow 

is stopped

1.  Low Flow Cuto

  

fl

 ow value is lower

than the zero 

fl

 ow noise level.

2.  Electrical noise is interfering with 

the measurement.

3.  Defective 2581 FlowtraMag.

1.  Adjust the Low Flow Cuto

  value to be above 

the noise level.

2. Verify/Modify 

Grounding.

3. Contact 

Technical 

Support.

Forgotten 
password

Forgotten/lost password

Connect blue wire to white wire while unit is powered 
(for 2 to 5 seconds.) Password will reset to factory 
original (last 6 digits of serial number.)

Summary of Contents for FlowtraMag GF 2581

Page 1: ...f reading accuracy Partially filled pipe detection status indicator Visual LED indicators make sensor status clear and easy to read Reverse flow direction configurable with 0252 Configuration Tool or...

Page 2: ...1 Depressurize and vent system prior to installation or removal 2 Confirm chemical compatibility before use 3 DO NOT exceed maximum temperature or pressure specs 4 ALWAYS wear safety goggles or face...

Page 3: ...ator Digital S3 L Output Digital S3 L 4 5 to 5 5 VDC Serial ASCII TTL level 9600 bps The Bluetooth word mark and logos are registered trademarks owned by Bluetooth SIG Inc and any use of such marks by...

Page 4: ...n 1 41 in 2X 0 22 in 3 91 in 5 46 in 9 82 in 7 86 0 062 in 199 6 1 6 mm 213 7 1 8 mm Pipe Cutout dimension 2X 28 8 mm 25 5 mm 35 8 mm 2X 5 5 mm 99 2 mm 249 4 mm 138 7 mm 3 91 in 9 82 in 5 46 in 2X 0 2...

Page 5: ...G ASTM and Metric pipe cutout dimensions are di erent DN80 Flange bolt kits and gaskets not shown Sold separately DN100 Flange bolt kits and gaskets not shown Sold separately 3 91 in 10 90 0 125 in 9...

Page 6: ...the 12 o clock position OK Recommended OK Vertical flow is OK IF the pipe remains FULL at all times DO NOT HANDLE BY THE SENSOR HEAD Always handle FlowtraMag Meters by the union nuts or flanges NOT t...

Page 7: ...nts 2 Select appropriate Metric or ASTM union end for installation 3 Install sensor with flow arrow pointing in the direction of flow Note Gland fittings should point upstream of flow 2581 FlowtraMag...

Page 8: ...440 713 FKM Profile Flange Gasket Metric 2 DN100 Metric Bolt Pattern Components Note Use M16 bolts Sold Separately Part Number Description Qty Req d 721 790 114 DN100 Flange Adapter PVC U Metric Use b...

Page 9: ...ronments connect the power cable shield drain wire to a clean low impedance earth ground If there is a single power supply for all 2581 FlowtraMag system components Instruments PLCs and VFDs route sig...

Page 10: ...g Tool App Default Configurations Wiring Configuration Continued DN25 1 in DN40 1 5 in DN50 2 in DN80 3 in DN100 4 in Units GPM GPM GPM GPM GPM Totalizer Units Gallons Gallons Gallons Gallons Gallons...

Page 11: ...ERED Signet Flow Instruments CAUTION Turn o Power before Wiring DO NOT REMOVE Seal Warranty void if seal is broken or removed WARRANTY VOID IF REMOVED Black Red Shield EMC enhancement 24 VDC 1A min Po...

Page 12: ...OR S3L Input 2 S3L Input 1 Frequency 1 S3 L 2 Ground White Data Red Output cable Black Brown Shield Blue not used Not used OR OR 2581 Ground White Data Red Output cable Black Brown Shield Blue not us...

Page 13: ...ual for Frequency wiring and programing instructions Wiring with Digital S3 L Output PWR 9900 Power Input LOOP LOOP PWR 9900 S3 L Terminal DATA GND V SHLD 9900 Transmitter S3L Freq 24 VDC 1A min Power...

Page 14: ...rn to home screen and look for App icon click the blue GF Config Tool icon 3 Continue to Sensor Setup Section next page Bluetooth App Setup Steps Android version Download the GF Configuration Tool App...

Page 15: ...ear Settings example shows Menu Android version Version 8 or newer When the 2581 FlowtraMag is in operation when in close proximity to the 2581 FlowtraMag less than 20 ft open the GF Config Tool App t...

Page 16: ...ly logs current screen view in real time when connected to the app App Configuration Monitor and Real Time Log Monitoring flow and totalizer Live Logging while connected to mobile tablet device set 1...

Page 17: ...saved settings configuration file See Save function above NOTE The file must be a GF Config Tool App settings configuration file The software will verify whether the user selected file is the correct...

Page 18: ...tal S3 L and Frequency and or 4 to 20 Active or Passive use the GF Config Tool App On the loop screen use the drop down to select digital S3 L or Freq and or Active or Passive 4 to 20 mA Press WRITE a...

Page 19: ...cable Black Brown Shield Blue not used Not used Ground White Data Red Bluetooth set to S L iOS device with home button Double click the home button Find the minimized app and swipe up to close the app...

Page 20: ...o tools that are designed to work around these deficiencies The Averaging and the Sensitivity features should be studied before making adjustments Averaging Time in Seconds Factory set Low Set the tim...

Page 21: ...tivity Low Flow Cut O and Direction of the Flow drop down menu 4 If the user has any correction or change you must Write the information to device then click Read device again 1 2 This is an outline F...

Page 22: ...on or change you must Write the information to device then click Read device again 5 The Loop tab select or confirm your 4 to 20 mA set point set your current alarm condition and type of output mode I...

Page 23: ...Tool 7 8 8 The Calibration tab allows custom calibration via method of rate volumetric zero flow calibration and reset flow calibration 7 The Monitor tab can graph or log the information to your local...

Page 24: ...0252 Configuration Tool 2 Check wiring Use the wiring diagram picture in the 2581 FlowtraMag manual Frequency Digital or Current Output is Erratic 1 Electrical Noise interference with the flow measure...