2581 FlowtraMag
®
Meter
Recommended:
The directional arrow should be pointed
DOWNSTREAM
for correct operation. If the 2581
FlowtraMag is installed on a vertical pipe, the cable
ports should be turned to point downward.
This will prevent condensation from being
channeled into the enclosure.
Application Tip:
If your
fl
ow is in the reverse direction, it is possible to set
up reverse
fl
ow via the GF Signet 0252 Con
fi
guration
Tool or GF Con
fi
g Tool App.
Default Con
fi
gurations
Wiring Con
fi
guration Continued
DN25 (1 in.)
DN40 (1.5 in.)
DN50 (2 in.)
DN80 (3 in.)
DN100 (4 in.)
Units
GPM
GPM
GPM
GPM
GPM
Totalizer Units
Gallons
Gallons
Gallons
Gallons
Gallons
K-Factor Values
852.716 pulse/gal
342.9120 pulse/gal
204.139 pulse/gal
91.0772 pulse/gal
52.1188 pulse/gal
Averaging
Low
Low
Low
Low
Low
Sensitivity
3.5182
8.7486
14.696
32.9390
57.561
Low Flow Cuto
ff
0.1407
0.3499
0.5878
1.3176
2.3024
4 mA Setpoint
0
0
0
0
0
20 mA Setpoint
70.3630
174.9718
293.9200
658.7815
1151.2153
Error Current
22
22
22
22
22
Passive/Active
Passive
Passive
Passive
Passive
Passive
S3L/Freq
Freq
Freq
Freq
Freq
Freq