2581 FlowtraMag
®
Meter
LED Status Indicators
10 s
2 s
20 s
30 s
40 s
50 s
60 s
70 s
NOTE:
The SENSITIVITY function is ine
ff
ective if the AVERAGING function is set to o
ff
(seconds).
No AVERAGING, no SENSITIVITY
AVERAGING only
AVERAGING and SENSITIVITY
With AVERAGING set to O
ff
and with SENSITIVITY set to zero, the
2581 FlowtraMag responds to every unstable shift in the
fl
ow.
The dashed red line represents the actual output of the
fl
ow sensor
in unstable
fl
ow conditions.
With AVERAGING set to Medium and SENSITIVITY still set to zero
the
fl
ow rate is stabilized, but a sharp change in
fl
ow rate is not
represented for 50 seconds or longer (dotted green line).
With AVERAGING at Medium and SENSITIVITY set to a moderate
amount, the
fl
ow rate is stabilized, while the sudden shift in
fl
ow is
re
fl
ected very quickly (solid blue line).
• Because ideal
fl
ow conditions are often impossible to achieve, the
fl
uids
fl
ow is often erratic, which causes erratic readings in
control features (e.g., relays, 4 to 20 mA loops, etc.) that are associated with the
fl
ow rate.
• The best solution to these problems is to correct any piping de
fi
ciency that causes the instability. This may involve longer
straight runs upstream, taking steps to ensure pipe remains full during
fl
ow conditions, and other installation changes.
In many situations, however, these measures are simply not possible.
• The 2581 FlowtraMag provides two tools that are designed to "work around" these de
fi
ciencies. The Averaging and the
Sensitivity features should be studied before making adjustments.
Averaging Time in Seconds (Factory set: Low)
• Set the time the meter will use as the averaging period. The ranges are O
ff
, Low (10 s), Med (40 s) and High (120 s).
Use higher averaging times to smooth the display and current output where the
fl
ow in the pipe is erratic.
Quick Response Sensitivity (Factory Set: 0.5 m/s (1.64 ft/s) equivalent)
•
Sets an amount of
fl
ow rate change at a given reference
fl
ow rate required to momentarily allow the 2581 FlowtraMag to change
from the selected averaging time to a faster response. The reference
fl
ow rate should be near the range of normal operation.
Turn the averaging setting to o
ff
and observe the
fl
ow rate variation, enter a sensitivity amount that is two times larger than the
amount of
fl
ow variation.
Averaging and Sensitivity Settings
LEDs on the 2581 FlowtraMag circuit board are useful to identify problems with the meter and the
fl
ow conditions.
LED Condition
Indication
All O
ff
The power is o
ff
or the sensor is not connected
Solid Blue
Normal operation, full pipe, no
fl
ow
Blinking Blue
Normal operation, blink rate is proportional to
fl
ow rate
Solid Purple
Partially
fi
lled pipe,
fl
ow rate is zero
Blinking Purple
Partially
fi
lled pipe, blink rate is proportional to
fl
ow rate
Blinking Red
Measurement out of range. If condition persists, will turn to solid red after 1 minute
Solid Red
Instrument error, defective electronic component. Contact Technical Support
Green
- Connected device
White
- No connections