130
AFE200 • Instruction Manual
Sys parameter
FB type
result
Count 32
32 bit
Receives 32 bits from FB and copies to 32 bits of monitor. OK
32_H
Receives 32 bits from FB and copies to 32 bits of monitor. OK
32_L
Receives 32 bits from FB and copies to 32 bits of monitor. OK
Count 16
16 bit
Receives 16 bits from FB and doesn’t know whether to copy to 16H or 16L of
monitor. Error
16_H
Receives 16 bits from FB and copies to 16H bit of monitor. OK
16_L
Receives 16 bits from FB and copies to 16L bit of monitor. OK
A
Fieldbus M->S X Mon
parameter can only be assigned to a single “
src
”. If assigned
to more than one
src
, an error signal is generated during fieldbus initialization.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
14.3.4
4026 FIeldbus M->S1 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.8
4036 FIeldbus M->S2 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.12 4046 FIeldbus M->S3 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.16 4056 FIeldbus M->S4 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.20 4066 FIeldbus M->S5 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.24 4076 FIeldbus M->S6 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.28 4086 FIeldbus M->S7 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.32 4096 FIeldbus M->S8 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.36 4106 FIeldbus M->S9 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.40 4116 FIeldbus M->S10 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.44 4126 FIeldbus M->S11 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.48 4136 FIeldbus M->S12 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.52 4146 FIeldbus M->S13 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.56 4156 FIeldbus M->S14 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.60 4166 FIeldbus M->S15 div
FLOAT
1.0
1.0
1000.0 ERW
14.3.64 4176 FIeldbus M->S16 div
FLOAT
1.0
1.0
1000.0 ERW
The
Div M->Sx fieldbus
parameters can be used to increase the resolution of the
datum sent on the bus to the
AFE
in the corresponding channel in EU and EU_float
exchange mode. The parameter value is used by the
AFE as the divider of the incom-
ing datum, so that a number with decimal digits can be transferred.
Note!
You must check the size in bits of the datum that is sent to make sure that the maximum value in bits
fits in a 16-bit integer. For example, if specifying the divider as “
Fieldbus M->Sn div
” = 1000, the
maximum value that can be used for the exchanged datum is 32.768 (32768/1000).
I.e. :
FIeldbus M->S1 div
= 10,
Fieldbus S->M1 ipa
=
Ramp ref src 1
,
Fieldbus
M->S1 sys
= Eu. If the PLC sends the decimal value 1000 on the first word the value
of
DC voltage ref src
on the AFE is 1000/10 = 100.
14.4 - COMMUNICATION/FIELDBUS S2M
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
14.4.1
4180 Fieldbus S->M1 ipa
FBM2SIPA
0
0
20000 RW
14.4.5
4190 Fieldbus S->M2 ipa
FBM2SIPA
0
0
20000 RW
14.4.9
4200 Fieldbus S->M3 ipa
FBM2SIPA
0
0
20000 RW
14.4.13 4210 Fieldbus S->M4 ipa
FBM2SIPA
0
0
20000 RW
14.4.17 4220 Fieldbus S->M5 ipa
FBM2SIPA
0
0
20000 RW
14.4.21 4230 Fieldbus S->M6 ipa
FBM2SIPA
0
0
20000 RW
14.4.25 4240 Fieldbus S->M7 ipa
FBM2SIPA
0
0
20000 RW
14.4.29 4250 Fieldbus S->M8 ipa
FBM2SIPA
0
0
20000 RW
14.4.33 4260 Fieldbus S->M9 ipa
FBM2SIPA
0
0
20000 RW
Summary of Contents for AFE200 4 Series
Page 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Page 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Page 203: ... AFE200 Instruction Manual 203 Commands ...
Page 204: ...204 AFE200 Instruction Manual Digital inputs ...
Page 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Page 206: ...206 AFE200 Instruction Manual Analog inputs ...
Page 207: ... AFE200 Instruction Manual 207 ...
Page 208: ...208 AFE200 Instruction Manual Analog outputs ...
Page 209: ... AFE200 Instruction Manual 209 Current Control ...
Page 210: ...210 AFE200 Instruction Manual Active Curr Config ...
Page 211: ... AFE200 Instruction Manual 211 Functions ...
Page 212: ......
Page 213: ......