AFE200 • Instruction Manual
87
3
4 kHz
4
6 kHz
5
8 kHz
6
10 kHz
7
12 kHz
8
16 kHz
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
4.11
564
Ambient temperature
ENUM
40 degC
0
1
ERWZ
Setting of the ambient temperature value. This parameter is used to set the output cur
-
rent derating factor (1% for every °C above 40°C).
0
40 degC
1
50 degC
40 degC
The AFE200 is capable of delivering direct current continuously with ambient
temperatures of up to 40°C.
50 degC
The AFE200 is capable of delivering direct current continuously with ambient
temperatures of up to 50°C.
If the value is set to 1 the AFE
output current will be 10% less than the rated current at 40°C.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
4.12
566
Drive overload mode
ENUM
Heavy duty
1
2
ERWZ
Setting of the overload that can be supplied by the
AFE, depending on the application.
1
Heavy duty
2
Light duty
Set
Heavy duty
when a large overload is requested: the
AFE can supply 180% of the
rated current for 0.5 seconds and 150% for 1 minute every 5 minutes.
Select
Light duty
to enable the
AFE to deliver a current of 110% of the rated current
for 1 minute every 5 minutes.
LCL must be ordered indicating the use of the AFE overload: Heavy Duty or Light
Duty. Changing the default value may impact on the LCL input filter operation.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
4.13
570
Password
UINT32
0
0
99999 ERW
You can enter a password to protect the parameters from unauthorized tampering: the
password can consist of a combination of a maximum of any 5 figures that can be se
-
lected by the user. All parameters are locked, except this one and
Save parameters
.
After entering the password, press the
E
key once to enter it into the memory and
again to enable it (= Enabled is displayed to indicate that the password is enabled).
So that the password remains valid even after switching the unit off and then switching
it back on, save it using the
Save parameters
command.
When the password is enabled any attempts to modify a parameter are blocked and
the
Password
enabled message is displayed.
To disable the password, enter the
Password
parameter (572) in the DRIVE CONFIG
menu.
Check that the password is enabled (
Enabled
), press
E
and enter the combination of
figures that make up the password.
Press
E
again. A message is displayed telling you the password is no longer enabled
(
Disabled
).
To make sure the password continues to be disabled even after switching the unit off and
then switching it back on, save this configuration using the
Save parameters
command.
When an incorrect password is entered, the
Password wrong
message is displayed.
Summary of Contents for AFE200 4 Series
Page 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Page 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Page 203: ... AFE200 Instruction Manual 203 Commands ...
Page 204: ...204 AFE200 Instruction Manual Digital inputs ...
Page 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Page 206: ...206 AFE200 Instruction Manual Analog inputs ...
Page 207: ... AFE200 Instruction Manual 207 ...
Page 208: ...208 AFE200 Instruction Manual Analog outputs ...
Page 209: ... AFE200 Instruction Manual 209 Current Control ...
Page 210: ...210 AFE200 Instruction Manual Active Curr Config ...
Page 211: ... AFE200 Instruction Manual 211 Functions ...
Page 212: ......
Page 213: ......