AFE200 • Instruction Manual
143
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.14
4570 Drive ovld activity
ENUM
Ignore
0
2
ERW
Setting of the behaviour of the AFE product in case of a
Drive overload [14]
alarm.
This alarm indicates that the AFE product overload threshold has been reached.
0
Ignore
1
Warning
2
Disable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.15
4582 HTsens restart
ENUM
Disable
0
1
ERW
Enabling of automatic restart after the AFE product heatsink overtemperature alarm
HeatsinkS OTUT [12]
.
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.16
4584 HTsens restart time
ms
UINT16
20000
120
60000 ERW
Setting of the time within which the
HeatsinkS OTUT [12]
alarm must be reset in
order to perform automatic restart.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.17
4600 InAir activity
ENUM
Disable
0
2
ERW
Setting of the behaviour of the AFE product in case of an intake air overtemperature
alarm
InAir [13]
. This alarm indicates that the temperature of the intake cooling air is
too high.
0
Ignore
1
Warning
2
Disable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.18
4602 InAir restart
ENUM
Disable
0
1
ERW
Enabling of automatic restart after the
Intakeair OT [13]
overtemperature alarm.
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.19
4604 InAir restart time
ms
UINT16
1000
120
30000 ERW
Setting of the time within which the
Intakeair OT [13]
alarm must be reset in order to
perform automatic restart.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.20
4606 Air holdoff
ms
UINT16
10000
0
30000 ERW
Setting of the delay between the signalling of the
Intakeair OT [13]
overtemperature
alarm
and enabling of the alarm. If an alarm condition occurs, the AFE product will
wait for the set time before enabling the alarm. If the alarm is removed within the set
time, the AFE product will not indicate any alarm condition.
Summary of Contents for AFE200 4 Series
Page 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Page 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Page 203: ... AFE200 Instruction Manual 203 Commands ...
Page 204: ...204 AFE200 Instruction Manual Digital inputs ...
Page 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Page 206: ...206 AFE200 Instruction Manual Analog inputs ...
Page 207: ... AFE200 Instruction Manual 207 ...