AFE200 • Instruction Manual
145
Setting of the time within which the
Undervoltage [2]
alarm must be reset in order to
perform automatic restart. (Time with alarm signal 100 msec).
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.29
4650 UVRep attempts
UINT16
5
0
1000
ERW
Setting of the maximum number of attempts at automatic restart after the
Undervolt-
age [2]
alarm before a
Mult
Undervoltage [6]
alarm is generated. If this parameter
is set to 1000 an infinite number of attempts are available.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.30
4652 UVRep delay
s
UINT16
240
0
300
ERW
Setting of the time within which, if no automatic restarts are executed after the
Und-
ervoltage [2]
alarm, the attempts counter is reset. In this way the number of attempts
set in
UVRep attempt
are still available.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.31
4670 Optionbus activity
ENUM
Disable
0
2
ERW
Setting of the behaviour of the AFE product in case of an
Opt Bus Fault [16]
alarm
.
0
Ignore
1
Warning
2
Disable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.32
4690 ExtIO activity
ENUM
Disable
0
2
ERW
This parameter is used to configure the behaviour of the drive if the “
Ext I/O fault
” [27]
alarm occurs when the EXP-FL-XCAN-ADV card is installed.
See Chapter 9 - “
Ext I/O fault
” [27] alarm.
When the alarm is activated due to a communication error, the last value that was
received is maintained.
The following activities are programmable:
0
Ignore
1
Warning
2
Disable
You can check whether a card that supports XCAN External IO functions is installed
from the DRIVE INFO menu for parameters 530, 532, 534 SlotX card type:
Value
Description
Expansion
832
IO FastLink
EXP-FL-XCAN-ADV
XCAN External IO supported
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.33
4940 FL fault activity
ENUM
Disable
0
2
ERW
This parameter is used to configure the behaviour of the drive when the “
FastLink
fault
” [28] alarm occurs.
If the EXP-FL-XCAN-ADV card is installed in the drive, all the FastLink communica
-
tion fault signals are enabled and managed via generation of a “
FastLink fault
” [28]
alarm, with different subcodes to indicate the cause of the error.
See Chapter 9 - “
FastLink Fault
” [28] alarm.
Summary of Contents for AFE200 4 Series
Page 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Page 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Page 203: ... AFE200 Instruction Manual 203 Commands ...
Page 204: ...204 AFE200 Instruction Manual Digital inputs ...
Page 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Page 206: ...206 AFE200 Instruction Manual Analog inputs ...
Page 207: ... AFE200 Instruction Manual 207 ...
Page 208: ...208 AFE200 Instruction Manual Analog outputs ...
Page 209: ... AFE200 Instruction Manual 209 Current Control ...
Page 210: ...210 AFE200 Instruction Manual Active Curr Config ...
Page 211: ... AFE200 Instruction Manual 211 Functions ...
Page 212: ......
Page 213: ......