AFE200 • Instruction Manual
141
Alarm
PAR
Ignore
Warning
Disable drive
ExtIO activity
4690
√
√
√
FL fault activity
4940
√
√
√
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.1
4500 Fault reset src
LINK
16BIT
1120
0
16384
RW
DIGSEL2
Selection of the origin (source) of the signal to be used for the command to reset the
AFE product after an alarm. The terminal that can be used for this function can be
selected from among those listed in the “L_DIGSEL2” selection list.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.2
4502 ExtFlt src
LINK
16BIT
6000
0
16384
RW
DIGSEL2
Selection of the origin (source) of the signal to be used as the input for the AFE prod
-
uct
External Fault [20]
alarm. The terminal that can be used for this function can be
selected from among those listed in the “L_DIGSEL2” selection list.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.3
4498 Precharge fbk src
LINK
16BIT
1112
0
16384
RW
L�DIGSEL1
Setting of the origin for the signal to confirm the pre-load contactor. If no confirmation
is received after a 100ms hold-off time the
Prc fbk loss
[23] alarm is generated (Pre-
load not confirmed).
If this parameter is set to
Precharge Command
(PAR 1122) the command and confir
-
mation always correspond and the alarm signal is never activated.
Starting from AFE with FW version 7.1,X this command is no more used with
precharge kit.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.4
4504 ExtFlt activity
ENUM
Disable
0
2
RW
Setting of the behaviour of the AFE product in the event of an external fault alarm
External Fault [20].
This alarm indicates the intervention of a AFE product external
protection.
0
Ignore
1
Warning
2
Disable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.5
4506 ExtFlt restart
ENUM
Disabilita
0
1
RW
Enabling of automatic restart after the external fault alarm
External Fault [20]
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.6
4508 ExtFlt restart time
ms
UINT16
1000
120
30000
RW
Setting of the time within which the
External Fault [20]
alarm must be reset in order to
perform automatic restart.
Summary of Contents for AFE200 4 Series
Page 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Page 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Page 203: ... AFE200 Instruction Manual 203 Commands ...
Page 204: ...204 AFE200 Instruction Manual Digital inputs ...
Page 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Page 206: ...206 AFE200 Instruction Manual Analog inputs ...
Page 207: ... AFE200 Instruction Manual 207 ...
Page 208: ...208 AFE200 Instruction Manual Analog outputs ...
Page 209: ... AFE200 Instruction Manual 209 Current Control ...
Page 210: ...210 AFE200 Instruction Manual Active Curr Config ...
Page 211: ... AFE200 Instruction Manual 211 Functions ...
Page 212: ......
Page 213: ......