Warning! Total current output cannot exceed total
current input rating!
There are different GFCI models used on the market.
See manufacture's instructions that come with the GFCI for
specific information. Note that all illustrations are examples only.
From
electrical box
To spa
Ground
wire
Main electrical box
GFCI panel
Verify if GFCI is properly connected.
If it's not, verify GFCI diagram and reconnect it.
Verify in.xe™ pack wiring (make sure that the neutral and the
ground have not been inverted).
From
electrical box
To spa
Important
connections:
Neutral of
GFCI must be
connected to
neutral bus.
Neutral from
spa must be
connected to
breaker.
If the GFCI is properly connected but still tripping, unplug all
outputs from the Spa Pack (pumps, blower, heater, ozonator etc).
Reconnect one output at the time until the GFCI trips again.
Replace defective component.
Note: Incorrect GFCI wiring may lead to a condition where the
GFCI may NOT trip when it should. Therefore, causing electrical
shock hazard. All electrical installations should be done by
qualified personnel only.
gfci trips