background image

11

geappliances.com

System Essential Components and Installation 

Unit including sleeve and 

front panel

The unit is packaged with the 
case and the front panel in place 
(filter not included). Installation 
begins by removing the front 
panel and pulling the unit out 
of the case. The empty case is 
positioned on the platform in 
the closet with the outdoor side 
facing the wall plenum opening 

(remove the side panel if a side installation is to be made) and 
secured to the plenum with six field supplied screws (stainless 
recommended).
Level the case using the four leveling legs and, using the holes 
in the bottom of the case as guides, drill holes in the mounting 
platform to secure the case to the platform. Use four field-
supplied bolts, washers and nuts to secure the case to the 
mounting platform. Do not tighten the bolts to the point of 
distorting the case.  
Failure to secure the case to the platform may result in 
excessive unit vibration and increased noise level. Install 
the unit into the case, either through the front or side panel 
opening. With the unit in position in the case, replace the side 
panel (if removed) and the front panel. Ground the unit to the 
case by installing the front unit-to-case hex bolt and/or the 
case-to-unit side screw (only on side installs).
The drain connection is made by connecting a 90

o

 PVC  

elbow to the unit’s female 3/4" NPT drain connector. The other 
end of the elbow is used to run the drain to either the internal 
or external drain.
The unit is shipped with a secondary drain hole. This drain hole 
is shipped open and must either be plugged or connected to 
an independent drain system. If a secondary drain system is 
used, attach a 90° schedule 40 PVC elbow to the secondary 
drain hole directed toward the secondary drain system. If a 
secondary drain system is NOT used, install a 3/4" schedule 
40 PVC plug to cap the hole. 

Ensure drain lines going out the 

plenum are sloped downward to allow water to drain out.
A 10" diameter flange on the top of the unit is used to connect 
to field supplied, insulated, flexible or rigid transition duct with 
an adjustable ring clamp. 
Flexible duct may be used for transitions only. Rigid duct must 
be used for 90

o

 bends and tees. Do not use flexible duct for 

unsupported runs of five feet or more.

Power Connection Kit

The ZVAC units have a universal heater assembly that is 
capable of producing electric resistance heat that can operate 
on a 15-amp, 20-amp, or 30-amp circuit. The amount of 
resistance heat is determined by the selection of the correct 
power connection kit. This is the same type of connection  
used by GE for years in the Premium and Deluxe series of the 
Zoneline units.

Units installed on 230 or 208-volt circuits may be line cord 
connected by plugging the line cord into a wall-mounted  
receptacle in the enclosure closet or directly connected.   
All ZVAC units come with a unit mounted junction box 
to contain the wiring connections if a direct connection 
installation is required. The same power connection kit is 
used for line cord connection or to make a direct connection. 
Instructions for making a direct connection on 230 or 208-volt 
circuits are included in the unit installation instructions.
Units installed on a 265-volt circuit must be direct connected 
in accordance with National Electrical Code. All ZVAC units 
come with a unit mounted junction box to contain the wiring 
connections when direct connection installation is made.  
For more information, see Power Connection kits on page 12.

Return air grille, access panel or  

louvered closet door

The return air from the room to the unit  
may enter the enclosure closet through 
one of four ways. A louvered door may be 
installed on the closet to allow return air to 
enter the closet through the louvers. When 
a louvered door is used, the filter would be 
installed in the filter bracket on the front 
panel of the unit. 
A wall-mounted access panel may be 
used instead of the louvered door. In this 

installation access to the unit is through a wall-mounted 
access panel rather than a door. The return air is through the 
panel. The access panel, model RAVRG1, requires a 28" wide by 
48" high cutout in the wall and there is a filter bracket behind 
the grille louvers.
The return air grille, model RAVRG2, may also be used and  
is designed to be installed in a 20 3/8" by 20 3/8" cutout in a  
flush closet door. In this installation, a filter can fit into the 
bracket in the RAVRG2.
A field-supplied return air grille, with a minimum dimension of 
20" by 20", may be used if mounted in a cutout in the door or 
wall. When employing this method for return air, the filter is 
installed in the bracket mounted on the unit.

Remote Thermostat

The ZVAC units are controlled by a 
wall-mounted thermostat. GE offers 
a complete line of thermostats to 
interface with the units or most 24-VAC 
thermostats may be used. If a non-GE 

thermostat is used, the compatibility of the thermostat with the 
unit is the responsibility of the installer. The unit has an integral 
transformer and no external voltage or transformer may be used.

Summary of Contents for Zoneline

Page 1: ...GE Zoneline vertical packaged terminal air conditioners 2010 Architects and Engineers Data Manual...

Page 2: ...cooling with electric resistance heat H heat pump with electric resistance heat W Cool only Zoneline packaged terminal unit Voltage Phase Frequency D 230 208 Volt single phase 60 Hz E 265 Volt single...

Page 3: ...rm Specifications 17 Additional Specifications 18 Warranty 19 Important Notice Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed Pr...

Page 4: ...mounted under the window there are limitations to furniture placement and curtains cannot hang to the floor Finally some people find the controls difficult to adjust for the desired temperature To ad...

Page 5: ...dehumidification Unique sleeve design for easier installation and service Three way slide out chassis service maintenance flexibility Electronic Temperature Limiting requires room air temperature sen...

Page 6: ...Temperature Limiting feature requires the use of the optional room air temperature sensor model RAVRMS Designed to be mounted on the wall of the unit enclosure closet the Room Air Temperature Sensor a...

Page 7: ...mmends a 28 wide door A 20 3 8 wide by 20 3 8 high cutout is required in the door to accommodate the grille and filter bracket Only one filter is to be used in the installation Multiple filters will r...

Page 8: ...in operating conditions frost can form on the indoor coil of an air conditioner reducing air flow and causing a lack of cooling complaint In order to prevent frost from forming the ZVAC has an automat...

Page 9: ...he room through this screened vent opening is not conditioned This unconditioned air becomes mixed with the conditioned air that is circulated by the ZVAC indoor fan This air mixture generates an addi...

Page 10: ...to raise the platform a minimum of 8 12 recommended and have a minimum load bearing capacity of 175 pounds The platform legs must be positioned so access to the unit drain connection is not blocked C...

Page 11: ...20 amp or 30 amp circuit The amount of resistance heat is determined by the selection of the correct power connection kit This is the same type of connection used by GE for years in the Premium and De...

Page 12: ...For all installations feeder sub feeder branch circuit and electrical protective devices must conform to all local codes In the absence of a local code the National Electrical Code should be followed...

Page 13: ...ger 9k 12k and 18k models only 14 RAVHW3 Hydronic kit triple row heat exchanger 12k and 18k models only 14 Unit Specifications AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC 230 208...

Page 14: ...ltage 60 Hertz 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Heating capacity designed to meet standard ARI rating conditions of 200 F water entering temp 180 F water exiting temp 70 F enter...

Page 15: ...Thermostat Heat Cool Hydronic Models 4 wire 5 wire Heat Pump Models 6 wire 6 wire Check the thermostat instructions for correct wiring and installation requirements 30 50 22 1 2 22 1 2 Cutout Dimensio...

Page 16: ...ough SIDE of case 3 min from two sides of case Plenum cutout 32 1 4 H x 20 W Drain fitting 3 4 Drain line Outside wall Platform Wall plenum Field supplied outer flashing A B A Minimum recommended acce...

Page 17: ...have a positive cooling condensate disposal system which meets the test requirements of applicable A R I standard 310 380 and 390 The disposal system shall have a slinger ring on the outdoor fan to di...

Page 18: ...dditional Specifications Service Submit complete information with bid covering service availability to whom service on units will be assigned complete address and phone number including phone number o...

Page 19: ...cessary maintenance Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Failure or damage resulting from corrosion due to installation in a...

Page 20: ...GE tradition of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2010 General Ele...

Reviews: