2
Electric resistance heat
Heat pumps
265 Volt Models
AZ85E09EAC AZ85E12EAC AZ85E18EAC AZ85H09EAC AZ85H12EAC AZ85H18EAC
Features
BTUH
9,000
11,700
17,900
8,800
11,700
17,800
E.E.R.
10.5
10.6
9.3
10.5
10.6
9.3
Dehumidification (pints/hr.)
2.5
3.2
5.0
2.5
3.2
5.0
Universal Heater (kW)
2.71/3.55/5.03 2.71/3.55/5.03 2.71/3.55/5.03 2.71/3.55/5.03 2.71/3.55/5.03 2.71/3.55/5.03
Reverse Cycle (BTUH)
N/A
N/A
N/A
8,200
10,400
16,400
COP @ 47°
N/A
N/A
N/A
3.4
3.4
3.0
SHR
0.82
0.80
0.70
0.83
0.79
0.70
Indoor CFM (Hi/Med/Low)
0.0" ESP
520/460/360
590/500/380
600/520/400
520/460/360
590/500/380
600/520/400
265 Volt available by special order.
Specifications
Other components are necessary for a complete
installation - see System Essential Components section.
Zoneline
®
Vertical Unit Nomenclature
The Zoneline vertical unit is identified by a model number defining the type of unit, cooling capacity, and electrical information.
When specifying or ordering the Zoneline Vertical unit the use of this nomenclature will assure receiving the correct unit.
EXAMPLE
Listed by
Underwriters'
Laboratories.
A
Z
8
5
E
0
9
D
A
C
Chassis series
85=vertical
Unit type
E= cooling with electric
resistance heat
H= heat pump with electric
resistance heat
W=Cool only
Zoneline
®
packaged
terminal unit
Voltage/Phase/Frequency
D= 230/208 Volt, single phase, 60 Hz
E= 265 Volt, single phase, 60 Hz
Heater
configuration
A= Universal heater
See power
connection kits
section
Nominal cooling capacity
09=8,800 BTUH cooling
12=11,700 BTUH cooling
18=17,900 BTUH cooling
Special Features
C= corrosion protection
Electric resistance heat
Heat pumps
Cool only
230/208 Volt Models
AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC AZ85W09DAC AZ85W12DAC AZ85W18DAC
Features
BTUH
9,000/8,800
11,700/11,500 17,900/17,700
8,800/8,600
11,700/11,500 17,800/17,700
9,000/8,800
11,700/11,500 17,900/17,700
E.E.R. (BTUH/Watt)
10.5/10.5
10.6/10.6
9.3/9.3
10.5/10.5
10.6/10.6
9.3/9.3
10.5/10.5
10.6/10.6
9.3/9.3
Dehumidification (pints/hr.)
2.5
3.2
5.0
2.5
3.2
5.0
2.5
3.2
5.0
Universal Heater (kW
@ 230 volts)
2.61/3.42/4.81 2.61/3.42/4.81 2.61/3.42/4.81 2.61/3.42/4.81 2.61/3.42/4.81 2.61/3.42/4.81
N/A
N/A
N/A
Reverse cycle (BTUH)
N/A
N/A
N/A
8,200/8,000
10,400/10,300 16,400/16,200
N/A
N/A
N/A
COP @ 47°
N/A
N/A
N/A
3.4
3.4
3.0
N/A
N/A
N/A
SHR
0.81
0.79
0.71
0.83
0.79
0.69
0.81
0.79
0.71
Indoor CFM (Hi/Med/Low)
0.0" ESP
520/460/360
590/500/380
600/520/400
520/460/360
590/500/380
600/520/400
520/460/360
590/500/380
600/520/400