background image

6

Features and Benefits

Excellent efficiency and dehumidification

GE recognizes the importance of energy efficiency and 
dehumidification in an air conditioning system and uses  
EER (Energy Efficiency Rating) as a means of reporting the 
relative cooling efficiency of the unit.
EER is the rating system used for Packaged Terminal Air 
Conditioners and Heat Pumps.
The GE Zoneline

®

 Vertical Packaged Terminal Heat Pump has 

outstanding COP ratings. The measurement of the efficiency  
of the heat pump output, when compared to electric resistance 
heat, is called the Coefficient of Performance (COP). This 
number provides a basis not only for comparing the heat  
pump output to electric resistance heat, but also the ability  
to directly compare heat pumps with the same range of 
capacity to one another.

Unique Sleeve Design

The ZVAC case is installed on a field supplied platform and  
attached to the wall plenum with field supplied screws. See 
pages 10 and 16 for platform construction details.
The chassis slides into the sleeve, allowing for easy removal  
of the unit for servicing and cleaning without the need to 
remove condensate lines.

Three-Way Slide-Out Chassis

The case is designed to allow the installation of the chassis 
from the front or either side of the case. This provides greater 
flexibility in building and room design and unit placement. If 
access to the front of the unit is restricted by a wall or furniture 
placement, the chassis can slide in from either side of the case. 
If an alcove or offset is designed into the building facade, 
the three-way slide-out chassis enables the unit to be easily 
installed and removed for service.

Electronic Temperature Limiting 

Although the vertical unit is controlled by a wall mounted 
thermostat, there may be a need to prevent the temperature 
from being set to extreme energy wasting settings. The ZVAC 
unit has seven independent programmable heating and 
cooling temperature limits. A wide selection of limits eliminates 
the need to reset the limits seasonally. 

The Temperature 

Limiting feature requires the use of the optional room 

air temperature sensor, model RAVRMS. Designed to be 
mounted on the wall of the unit enclosure closet, the Room Air 
Temperature Sensor allows any compatible thermostat to be 
used with the unit and provide Temperature Limiting. 
 
The limits are set by dip switches located on the ZVAC unit and 
are not accessible by the room occupant. Location of the dip 
switches and the temperature settings are shown on page 14. 

Cooling Temperature Limits degrees F.

Min 

60°  64° 

66° 

68° 

70° 

72°  74°  76°

Max  85°  85° 

85° 

85° 

85° 

85° 

85°  85°

 

Heating Temperature Limits degrees F.

Min 

60°  60° 

60° 

60° 

60° 

60°  60°  60°

Max  85°  80° 

78° 

76° 

74° 

72°  70°  65°

Freeze Sentinel

To prevent damage to plumbing and room furnishings by 
freezing temperatures, the ZVAC unit can provide Freeze 
Sentinel which turns the resistance heaters on at 41° F.,  
warms the indoor air to 46° F., and shuts the heater off.   

The Freeze Sentinel feature requires the use of the  

optional Room Air Temperature Sensor, model RAVRMS. 
Designed to be mounted on the room side wall of the unit 
enclosure closet, the Room Air Temperature Sensor allows any 
compatible thermostat to be used with the unit and  
provide Freeze Sentinel protection. The Freeze Sentinel 
protection is automatic with the installation of the RAVRMS. 
Even if the unit is connected to a Central Desk Control system 
or a Room Occupancy Sensor system, and the unit is turned 
off by the controlling system, Freeze Sentinel is still active to 
provide protection. It may be defeated by switching the unit’s 
ON/OFF switch to the OFF position, removing the power supply 
to the unit or putting #2 dip switch in DOWN position.

Constant ON fan 

Some localities may require the indoor fan on Packaged 
Terminal Air Conditioners to operate at all times, even when 
the wall primary control would normally turn the unit off. To 
accommodate this requirement and provide the feature for  
use by anyone wanting to operate the unit in this manner,  
GE has provided a switch on the ZVAC that will allow this  
mode of fan operation. 
If the controlling dip switch (#3) is set in the UP setting, the fan  
will run unless the unit’s ON/OFF switch is set to the OFF 
position or power is removed from the unit.

Summary of Contents for Zoneline

Page 1: ...GE Zoneline vertical packaged terminal air conditioners 2010 Architects and Engineers Data Manual...

Page 2: ...cooling with electric resistance heat H heat pump with electric resistance heat W Cool only Zoneline packaged terminal unit Voltage Phase Frequency D 230 208 Volt single phase 60 Hz E 265 Volt single...

Page 3: ...rm Specifications 17 Additional Specifications 18 Warranty 19 Important Notice Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed Pr...

Page 4: ...mounted under the window there are limitations to furniture placement and curtains cannot hang to the floor Finally some people find the controls difficult to adjust for the desired temperature To ad...

Page 5: ...dehumidification Unique sleeve design for easier installation and service Three way slide out chassis service maintenance flexibility Electronic Temperature Limiting requires room air temperature sen...

Page 6: ...Temperature Limiting feature requires the use of the optional room air temperature sensor model RAVRMS Designed to be mounted on the wall of the unit enclosure closet the Room Air Temperature Sensor a...

Page 7: ...mmends a 28 wide door A 20 3 8 wide by 20 3 8 high cutout is required in the door to accommodate the grille and filter bracket Only one filter is to be used in the installation Multiple filters will r...

Page 8: ...in operating conditions frost can form on the indoor coil of an air conditioner reducing air flow and causing a lack of cooling complaint In order to prevent frost from forming the ZVAC has an automat...

Page 9: ...he room through this screened vent opening is not conditioned This unconditioned air becomes mixed with the conditioned air that is circulated by the ZVAC indoor fan This air mixture generates an addi...

Page 10: ...to raise the platform a minimum of 8 12 recommended and have a minimum load bearing capacity of 175 pounds The platform legs must be positioned so access to the unit drain connection is not blocked C...

Page 11: ...20 amp or 30 amp circuit The amount of resistance heat is determined by the selection of the correct power connection kit This is the same type of connection used by GE for years in the Premium and De...

Page 12: ...For all installations feeder sub feeder branch circuit and electrical protective devices must conform to all local codes In the absence of a local code the National Electrical Code should be followed...

Page 13: ...ger 9k 12k and 18k models only 14 RAVHW3 Hydronic kit triple row heat exchanger 12k and 18k models only 14 Unit Specifications AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC 230 208...

Page 14: ...ltage 60 Hertz 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Heating capacity designed to meet standard ARI rating conditions of 200 F water entering temp 180 F water exiting temp 70 F enter...

Page 15: ...Thermostat Heat Cool Hydronic Models 4 wire 5 wire Heat Pump Models 6 wire 6 wire Check the thermostat instructions for correct wiring and installation requirements 30 50 22 1 2 22 1 2 Cutout Dimensio...

Page 16: ...ough SIDE of case 3 min from two sides of case Plenum cutout 32 1 4 H x 20 W Drain fitting 3 4 Drain line Outside wall Platform Wall plenum Field supplied outer flashing A B A Minimum recommended acce...

Page 17: ...have a positive cooling condensate disposal system which meets the test requirements of applicable A R I standard 310 380 and 390 The disposal system shall have a slinger ring on the outdoor fan to di...

Page 18: ...dditional Specifications Service Submit complete information with bid covering service availability to whom service on units will be assigned complete address and phone number including phone number o...

Page 19: ...cessary maintenance Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Failure or damage resulting from corrosion due to installation in a...

Page 20: ...GE tradition of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2010 General Ele...

Reviews: