Additional Specifications For  
GE Vertical Zoneline

®

 Heat Pumps

Heat pump unit shall automatically switch from heat pump 
operation to electric resistance heat when it is unable to 
provide sufficient heat to maintain room temperature or  
when the outdoor temperature falls below 25°F.
Unit shall be equipped with a temperature activated valve  
to allow condensate water generated during defrost cycles  
to drain into the specified drain system.
Unit shall have a concealed switch to allow heat pump 
operation to be overridden and heat provided by electric 
resistance heaters regardless of outdoor temperatures. 
Heat pump unit shall have Reverse Cycle (hot gas) Defrost 
system to maximize heat pump operation and minimize 
energy consumption. 
To minimize energy consumption, units shall have electric 
heaters locked out when outdoor temperatures are above 
46°F. Heating will be provided by heat pump operation only.   
In the event of a compressor failure during heat pump 
operation, the unit shall automatically switch to electric 
resistance heat to maintain selected room temperature 
regardless of outdoor temperatures. 
When the heat mode is selected or when the unit is switched 
from off to on in heat mode, the unit shall energize electric 
heaters to quickly warm the room to wall thermostat set  
point. Heat pump operation will resume on subsequent 
heating requirements.
Unit shall have an indoor coil temperature sensor to protect 
the compressor when the outdoor temperatures are too high 
for heat pump operation.    

Additional Specifications Service

Submit complete information with bid covering service 
availability, to whom service on units will be assigned, 
complete address and phone number, including phone  
number of emergency service personnel.

Startup, Adjust, Demonstrate

Contractor shall be responsible for the initial starting of  
units, adjustments thereto, cleaning, etc.; to place the units  
in required operating condition. Contractor shall demonstrate 
to the owner, or his representative, the operation of units for 
both summer and winter functions.

Limited Warranty

For one year from date of original purchase, manufacturer 
will provide, free of charge, parts and service labor on site to 
repair or replace any part of the Zoneline that fails because of 
a manufacturing defect. 
For an additional four years from the date of original purchase, 
manufacturer will provide, free of charge, parts and on-site 
service labor to repair or replace any part of the sealed 
refrigerating system (compressor, condenser, evaporator, and 
all connecting tubing) that fails due to a manufacturing defect. 
For the second through fifth year from the date of original 
purchase, the manufacturer will provide a limited parts 
warranty. The manufacturer will provide, free of charge, 
parts that fail as a result of a manufacturing defect. Parts 
covered are fan motors, switches, heater, heater protectors, 
compressor overload, solenoids, circuit boards, auxiliary 
controls, thermistors, frost controls, capacitors, and varistors. 
This limited parts warranty does not include labor or 
transportation to and from the service shop.
All warranty service is to be provided by manufacturers 
factory service centers or by their authorized servicers during 
normal working hours.

Summary of Contents for Zoneline

Page 1: ...GE Zoneline vertical packaged terminal air conditioners 2010 Architects and Engineers Data Manual...

Page 2: ...cooling with electric resistance heat H heat pump with electric resistance heat W Cool only Zoneline packaged terminal unit Voltage Phase Frequency D 230 208 Volt single phase 60 Hz E 265 Volt single...

Page 3: ...rm Specifications 17 Additional Specifications 18 Warranty 19 Important Notice Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed Pr...

Page 4: ...mounted under the window there are limitations to furniture placement and curtains cannot hang to the floor Finally some people find the controls difficult to adjust for the desired temperature To ad...

Page 5: ...dehumidification Unique sleeve design for easier installation and service Three way slide out chassis service maintenance flexibility Electronic Temperature Limiting requires room air temperature sen...

Page 6: ...Temperature Limiting feature requires the use of the optional room air temperature sensor model RAVRMS Designed to be mounted on the wall of the unit enclosure closet the Room Air Temperature Sensor a...

Page 7: ...mmends a 28 wide door A 20 3 8 wide by 20 3 8 high cutout is required in the door to accommodate the grille and filter bracket Only one filter is to be used in the installation Multiple filters will r...

Page 8: ...in operating conditions frost can form on the indoor coil of an air conditioner reducing air flow and causing a lack of cooling complaint In order to prevent frost from forming the ZVAC has an automat...

Page 9: ...he room through this screened vent opening is not conditioned This unconditioned air becomes mixed with the conditioned air that is circulated by the ZVAC indoor fan This air mixture generates an addi...

Page 10: ...to raise the platform a minimum of 8 12 recommended and have a minimum load bearing capacity of 175 pounds The platform legs must be positioned so access to the unit drain connection is not blocked C...

Page 11: ...20 amp or 30 amp circuit The amount of resistance heat is determined by the selection of the correct power connection kit This is the same type of connection used by GE for years in the Premium and De...

Page 12: ...For all installations feeder sub feeder branch circuit and electrical protective devices must conform to all local codes In the absence of a local code the National Electrical Code should be followed...

Page 13: ...ger 9k 12k and 18k models only 14 RAVHW3 Hydronic kit triple row heat exchanger 12k and 18k models only 14 Unit Specifications AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC 230 208...

Page 14: ...ltage 60 Hertz 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Heating capacity designed to meet standard ARI rating conditions of 200 F water entering temp 180 F water exiting temp 70 F enter...

Page 15: ...Thermostat Heat Cool Hydronic Models 4 wire 5 wire Heat Pump Models 6 wire 6 wire Check the thermostat instructions for correct wiring and installation requirements 30 50 22 1 2 22 1 2 Cutout Dimensio...

Page 16: ...ough SIDE of case 3 min from two sides of case Plenum cutout 32 1 4 H x 20 W Drain fitting 3 4 Drain line Outside wall Platform Wall plenum Field supplied outer flashing A B A Minimum recommended acce...

Page 17: ...have a positive cooling condensate disposal system which meets the test requirements of applicable A R I standard 310 380 and 390 The disposal system shall have a slinger ring on the outdoor fan to di...

Page 18: ...dditional Specifications Service Submit complete information with bid covering service availability to whom service on units will be assigned complete address and phone number including phone number o...

Page 19: ...cessary maintenance Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Failure or damage resulting from corrosion due to installation in a...

Page 20: ...GE tradition of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2010 General Ele...

Reviews: