background image

9

geappliances.com

Features and Benefits

to operate this low because of the larger outdoor coil area 
and because central system heat pumps have a reverse cycle 
defrost mode that melts accumulated frost off the outdoor coil.
Other vertical packaged terminal heat pump units terminate 
heat pump operation and switch to more expensive resistance 
heat at outdoor temperatures in the 40°F. to 45°F. range. They 
must terminate heat pump operation before a frost build-up 
occurs on the outdoor coil since they have no way of eliminating 
the frost.
GE offers a reverse cycle defrost system, like the central systems, 
on all Zoneline Packaged Terminal Heat Pumps. This provides the 
owners with the savings realized by the ability to operate in heat 
pump mode to lower outdoor temperatures. GE has adapted the 
reverse cycle heat pump defrost system to the ZVAC for greater 
savings in heat pump mode.
The ZVAC will provide heat pump savings down to a 25°F. 
outdoor temperature. At temperatures below 25°F., the unit 
will automatically switch to electric heat. When the outdoor 
temperature rises to 32°F., the unit will automatically switch  
back to heat pump operation. As long as the heat pump output 
is able to maintain the room temperature within 2°F. of the 
thermostat set point, the unit will run in heat pump mode down 
to 25°F. outdoor air temperature. The resistance heater and the 
heat pump do not operate simultaneously.
If the outdoor temperature is above 25°F. and if the room 
temperature falls more than 2°F. below the set point, the 
thermostat automatically switches the unit to resistance heat. 
If frost develops on the outdoor coil at temperatures above 25°F., 
the unit initiates the reverse cycle defrost operation to warm the 
outdoor coil and allow the unit to resume heat pump operation.
Prior to initiating the defrost sequence, the electric heaters will 
be energized to bring the room to the thermostat set point. 
Immediately after the defrost is completed, the electric heaters 
are energized to bring the room back to room temperature. The 
defrost sequence is terminated when the outdoor coil reaches 
68°F. or when nine minutes has elapsed.

Concealed Manual Vent Control

Open ventilation doors on GE Vertical Zoneline

®

 Packaged 

Terminal Air Conditioners and Heat Pumps allow outside air to 
enter the room through a screen-covered opening in the weather 
barrier that separates the indoor and outdoor sections of the 
unit. For each cfm of air to enter the room, an equal amount of 
air must be removed through exhaust fans in the bathroom or 
roof tops. Outside ambient air entering the room through this 
screened vent opening is not conditioned. This unconditioned  
air becomes mixed with the conditioned air that is circulated  
by the ZVAC indoor fan. This air mixture generates an additional 
heat load/heat loss that causes the unit to run longer and may 
translate into higher operating costs.
A concealed lever located behind the front cover of the ZVAC  
is used to open and close the vent door. 

Zoneline vent openings 

are not intended to be the source of make-up air for building 

ventilation systems due to the additional heating or cooling  

loads generated.

Ventilation CFM at various ESP points:

 

Warranty (including both parts and labor)

GE has provided the most comprehensive warranty available, 
without additional charge, on a vertical packaged terminal unit.
The entire warranty covering the ZVAC unit is printed in the back 
of this manual but the highlights are:

•  Limited One-Year Warranty - covering any part that fails 

as a result of a defect in materials or workmanship - parts, 

labor, and on-site service free of charge.

•  Limited Additional Four-Year Warranty - covering any part 

 

of the sealed refrigerating system (Compressor, condenser, 

evaporator, and all connecting tubing) that fails due to  

a defect in materials or workmanship - parts, labor, and  

on-site service free of charge.

•  Limited Parts Warranty for 2nd - 5th Year - covering fan 

motors, switches, heater, heater protectors, compressor 

overload, solenoids, circuit boards, auxiliary controls, 

thermistors, frost controls, capacitors and resistors. This  

is a limited warranty and does not include labor or cartage.

System Essential Components  
and Installation 

Each Zoneline Vertical Packaged Terminal Air Conditioner  
or heat pump requires an installation platform, wall plenum, 
exterior grille, chassis including case, power connection kit, 
remote thermostat, filter and a return air grille, ductwork  
and supply registers. 
The installation platform, ductwork and supply registers are field 
supplied. Each of the other components is ordered separately. 
The wall plenum, exterior grille and power connection kit are 
specifically designed to interface with the GE ZVAC unit and 
must be purchased from the same source as the unit.
The remote thermostat and the return air grille are offered as 
accessories by GE, but may be purchased from a source other 
than GE. If a non-GE thermostat or return air grille is used, they 
must have the minimum requirements to work properly with 
the unit. The filter is a standard 20" x 20" x 1" filter available 
where air conditioner filters are sold. The room temperature 
sensor is an optional GE accessory available from the same 
source as the unit.

Ventilation (CFM)

static pressure

inch water

9000 BTU 12000 BTU 18000 BTU

230V

230V

230V

0.0

62

68

72

0.1

52

61

70

0.2

46

57

69

0.3

41

52

64

0.4

34

45

57

Summary of Contents for Zoneline

Page 1: ...GE Zoneline vertical packaged terminal air conditioners 2010 Architects and Engineers Data Manual...

Page 2: ...cooling with electric resistance heat H heat pump with electric resistance heat W Cool only Zoneline packaged terminal unit Voltage Phase Frequency D 230 208 Volt single phase 60 Hz E 265 Volt single...

Page 3: ...rm Specifications 17 Additional Specifications 18 Warranty 19 Important Notice Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed Pr...

Page 4: ...mounted under the window there are limitations to furniture placement and curtains cannot hang to the floor Finally some people find the controls difficult to adjust for the desired temperature To ad...

Page 5: ...dehumidification Unique sleeve design for easier installation and service Three way slide out chassis service maintenance flexibility Electronic Temperature Limiting requires room air temperature sen...

Page 6: ...Temperature Limiting feature requires the use of the optional room air temperature sensor model RAVRMS Designed to be mounted on the wall of the unit enclosure closet the Room Air Temperature Sensor a...

Page 7: ...mmends a 28 wide door A 20 3 8 wide by 20 3 8 high cutout is required in the door to accommodate the grille and filter bracket Only one filter is to be used in the installation Multiple filters will r...

Page 8: ...in operating conditions frost can form on the indoor coil of an air conditioner reducing air flow and causing a lack of cooling complaint In order to prevent frost from forming the ZVAC has an automat...

Page 9: ...he room through this screened vent opening is not conditioned This unconditioned air becomes mixed with the conditioned air that is circulated by the ZVAC indoor fan This air mixture generates an addi...

Page 10: ...to raise the platform a minimum of 8 12 recommended and have a minimum load bearing capacity of 175 pounds The platform legs must be positioned so access to the unit drain connection is not blocked C...

Page 11: ...20 amp or 30 amp circuit The amount of resistance heat is determined by the selection of the correct power connection kit This is the same type of connection used by GE for years in the Premium and De...

Page 12: ...For all installations feeder sub feeder branch circuit and electrical protective devices must conform to all local codes In the absence of a local code the National Electrical Code should be followed...

Page 13: ...ger 9k 12k and 18k models only 14 RAVHW3 Hydronic kit triple row heat exchanger 12k and 18k models only 14 Unit Specifications AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC 230 208...

Page 14: ...ltage 60 Hertz 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Heating capacity designed to meet standard ARI rating conditions of 200 F water entering temp 180 F water exiting temp 70 F enter...

Page 15: ...Thermostat Heat Cool Hydronic Models 4 wire 5 wire Heat Pump Models 6 wire 6 wire Check the thermostat instructions for correct wiring and installation requirements 30 50 22 1 2 22 1 2 Cutout Dimensio...

Page 16: ...ough SIDE of case 3 min from two sides of case Plenum cutout 32 1 4 H x 20 W Drain fitting 3 4 Drain line Outside wall Platform Wall plenum Field supplied outer flashing A B A Minimum recommended acce...

Page 17: ...have a positive cooling condensate disposal system which meets the test requirements of applicable A R I standard 310 380 and 390 The disposal system shall have a slinger ring on the outdoor fan to di...

Page 18: ...dditional Specifications Service Submit complete information with bid covering service availability to whom service on units will be assigned complete address and phone number including phone number o...

Page 19: ...cessary maintenance Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Failure or damage resulting from corrosion due to installation in a...

Page 20: ...GE tradition of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2010 General Ele...

Reviews: