Features and Benefits

3-Speed Indoor Fan Motor  

for selectable HIGH and LOW speeds

Since the ZVAC discharge air may be routed through duct  
work for air distribution into the room and into other rooms,  
the units are equipped with a 3-speed fan to provide greater 
air movement, to compensate for the additional duct length. 
GE recommends an HVAC engineer be consulted to determine 
the best fan speed for the application.
A switch on the unit (dip switch #5-duct) adjusts the two-speed 
fan system to different settings. With the switch in the UP 
position, the system will operate using high and medium fan 
speeds. With the switch in the DOWN position, the system will 
operate using the medium and low fan speeds.
For example, on the 9,000 BTUH unit, the three fan speeds at 
0.2" ESP provide 220 CFM on the lowest fan speed, 370 CFM on 
the medium fan speed, and 480 CFM on the highest fan speed.
With the switch down, the unit would provide 220 CFM on  
LOW speed and 370 CFM on HIGH speed. With the switch up, 
the unit would provide 370 CFM on LOW speed and 480 CFM  
on HIGH speed. 
Higher CFMs tend to increase the operating sound level, both 
from fan noise and from the air noise in the duct. Higher CFMs 
also reduce the dehumidification rate of the unit, while lower 
CFMs provide quieter operation and better dehumidification. 
However, if the CFMs are not high enough to adequately move 
the air through the duct system, the unit will not be able to 
provide a comfortable room. 

Corrosion Protection Treatment (Standard) 

All ZVAC units are protected 
against damage from seacoast 
area corrosion. Components 
that are in contact with the 
salt air have special coatings 
or are made of non-corroding 
materials to help withstand 
the corrosive effects of the 
environment. This protection 
includes the use of totally 
enclosed fan motors with 
painted casings, a special 

coating on the outdoor coil, use of stainless steel screws and 
brackets, and additional paint on components like the base pan.

Slinger Ring Condensate Removal 

Condensate water removed from the indoor air is dispersed 
into the air stream by the outdoor fan slinger ring and 
deposited on the hot outdoor coil. The water helps cool the 
refrigerant in the outdoor coil and increases the efficiency of 
the air conditioner.

Indoor Coil Frost Control

Under certain operating conditions, frost can form on the indoor 
coil of an air conditioner, reducing air flow, and causing a lack 
of cooling complaint. In order to prevent frost from forming, the 
ZVAC has an automatic frost control on the indoor coil. When 
frost begins to form on the coil, the compressor stops until the 
coil temperature increases and the frost dissipates. 
At this time, the compressor resumes operation and cooling 
continues. The indoor fan remains running during the time  
the compressor is off to help warm the coil with room 
temperature air.

Automatic Compressor Random Restart 

In the event of a power interruption, all compressors 
attempting to restart immediately when power is restored  
can result in a power surge that can cause another power 
failure. The microprocessor in the ZVAC unit has a random 
restart logic system that prevents all compressors from 
restarting at the same instant.

Compressor Restart Delay

ZVAC units are designed to provide a minimum of three 
minutes of compressor off time to allow refrigerant pressures 
to equalize before attempting to restart. Attempting to restart 
against a high head pressure shortens compressor and 
overload protector life.
The units are also designed to provide a minimum of three 
minutes of compressor run time to prevent short cycling from 
disturbing the room occupant.

Quick Heat Recovery (On Heat Pump Units)

Heat pumps save money compared to electric resistance 
heat, but if the unit cannot provide room occupant comfort, 
the savings may be of questionable benefit. GE has years of 
experience with designing Zoneline heat pumps to solve the 
problem of guest complaints.
The heat pump unit incorporates a two-stage heat/one-stage 
cooling thermostat that utilizes the resistance heat to bring the 
room temperature to within 2°F. of the thermostat set point 
before initiating heat pump operation. This method addresses 
the two major complaints about heat pump operation: taking 
too long to warm the room and low discharge air temperature. 
Full electric resistance heat is utilized when the unit is first 
turned on or when the unit is operating in heat pump mode 
and the temperature in the room falls more than 2

°

F. below  

the thermostat set point.

Extended Heat Pump  

Operation/Reverse Cycle Defrost

Heat exists in the outdoor air at temperatures even below 0°F. 
Many central systems, with larger outdoor coils, operate in the 
heat pump mode down to temperatures in the mid-teens or 
even to single-digit temperatures. Central systems are able 

Summary of Contents for Zoneline

Page 1: ...GE Zoneline vertical packaged terminal air conditioners 2010 Architects and Engineers Data Manual...

Page 2: ...cooling with electric resistance heat H heat pump with electric resistance heat W Cool only Zoneline packaged terminal unit Voltage Phase Frequency D 230 208 Volt single phase 60 Hz E 265 Volt single...

Page 3: ...rm Specifications 17 Additional Specifications 18 Warranty 19 Important Notice Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed Pr...

Page 4: ...mounted under the window there are limitations to furniture placement and curtains cannot hang to the floor Finally some people find the controls difficult to adjust for the desired temperature To ad...

Page 5: ...dehumidification Unique sleeve design for easier installation and service Three way slide out chassis service maintenance flexibility Electronic Temperature Limiting requires room air temperature sen...

Page 6: ...Temperature Limiting feature requires the use of the optional room air temperature sensor model RAVRMS Designed to be mounted on the wall of the unit enclosure closet the Room Air Temperature Sensor a...

Page 7: ...mmends a 28 wide door A 20 3 8 wide by 20 3 8 high cutout is required in the door to accommodate the grille and filter bracket Only one filter is to be used in the installation Multiple filters will r...

Page 8: ...in operating conditions frost can form on the indoor coil of an air conditioner reducing air flow and causing a lack of cooling complaint In order to prevent frost from forming the ZVAC has an automat...

Page 9: ...he room through this screened vent opening is not conditioned This unconditioned air becomes mixed with the conditioned air that is circulated by the ZVAC indoor fan This air mixture generates an addi...

Page 10: ...to raise the platform a minimum of 8 12 recommended and have a minimum load bearing capacity of 175 pounds The platform legs must be positioned so access to the unit drain connection is not blocked C...

Page 11: ...20 amp or 30 amp circuit The amount of resistance heat is determined by the selection of the correct power connection kit This is the same type of connection used by GE for years in the Premium and De...

Page 12: ...For all installations feeder sub feeder branch circuit and electrical protective devices must conform to all local codes In the absence of a local code the National Electrical Code should be followed...

Page 13: ...ger 9k 12k and 18k models only 14 RAVHW3 Hydronic kit triple row heat exchanger 12k and 18k models only 14 Unit Specifications AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC 230 208...

Page 14: ...ltage 60 Hertz 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Heating capacity designed to meet standard ARI rating conditions of 200 F water entering temp 180 F water exiting temp 70 F enter...

Page 15: ...Thermostat Heat Cool Hydronic Models 4 wire 5 wire Heat Pump Models 6 wire 6 wire Check the thermostat instructions for correct wiring and installation requirements 30 50 22 1 2 22 1 2 Cutout Dimensio...

Page 16: ...ough SIDE of case 3 min from two sides of case Plenum cutout 32 1 4 H x 20 W Drain fitting 3 4 Drain line Outside wall Platform Wall plenum Field supplied outer flashing A B A Minimum recommended acce...

Page 17: ...have a positive cooling condensate disposal system which meets the test requirements of applicable A R I standard 310 380 and 390 The disposal system shall have a slinger ring on the outdoor fan to di...