The GE Zoneline

®

 Vertical Packaged Terminal Air Conditioner

The GE Zoneline

®

 vertical air conditioner is available in 8,800 BTUH, 11,700 BTUH or 17,800 BTUH cooling capacity with either 

resistance heat, cool only or heat pump units with resistance heat backup. Each cooling capacity is available in a dual rated 
unit that operates on either 230 volts or 208 volts and in a unit designed to operate on 265 (277) volts. All units, except cool only 
models are equipped with a 3-element universal heater that provides electric heat backup when connected with the appropriate 
9-pin power connection kit to 208-volt, 230-volt or 265(277) volt power. See page 12 for information on the power connection kits. 

System Features

The ZVAC has a number of features that help distinguish 
it as the leader in the vertical unit industry. Each feature is 
discussed in detail in the Features and Benefits section.

• Excellent efficiency and dehumidification
• Unique sleeve design for easier installation and service
• Three-way slide-out chassis service/maintenance flexibility
• Electronic Temperature Limiting (requires room air 

temperature sensor accessory - RAVRMS)

• Freeze Sentinel

 (requires room air temperature sensor 

accessory - RAVRMS)

• Constant ON fan (required in nursing homes in some states)
• Permanently Lubricated Fan Motors
• Standard Size Air Filter (20 x 20 x 1)
• Central Desk Control Capability
• Occupancy Sensor Interface
• HI and LOW fan speeds controlled by remote thermostat
• 3-Speed Indoor Fan Motor for selectable HI and LOW speeds
• Corrosion Protection Treatment Standard 
• Slinger Ring Condensate Removal 
• Indoor Frost Control
• Automatic Compressor Random Restart 
• Compressor Restart Delay
• Quick Heat Recovery (On Heat Pump Units)
• Extended Heat Pump Operation
• Reverse Cycle Heat Pump Defrost
• Warranty (including both parts and labor)

System Essential Components

• Installation Platform (field supplied)
• Wall Plenum
• Exterior Grille
• Chassis
• Case
• Power Connection Kit
• Remote Thermostat
• Filter (field supplied)
• Return Air Grille
• Ductwork (field supplied)
• Supply Register (field supplied)

Summary of Contents for Zoneline

Page 1: ...GE Zoneline vertical packaged terminal air conditioners 2010 Architects and Engineers Data Manual...

Page 2: ...cooling with electric resistance heat H heat pump with electric resistance heat W Cool only Zoneline packaged terminal unit Voltage Phase Frequency D 230 208 Volt single phase 60 Hz E 265 Volt single...

Page 3: ...rm Specifications 17 Additional Specifications 18 Warranty 19 Important Notice Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed Pr...

Page 4: ...mounted under the window there are limitations to furniture placement and curtains cannot hang to the floor Finally some people find the controls difficult to adjust for the desired temperature To ad...

Page 5: ...dehumidification Unique sleeve design for easier installation and service Three way slide out chassis service maintenance flexibility Electronic Temperature Limiting requires room air temperature sen...

Page 6: ...Temperature Limiting feature requires the use of the optional room air temperature sensor model RAVRMS Designed to be mounted on the wall of the unit enclosure closet the Room Air Temperature Sensor a...

Page 7: ...mmends a 28 wide door A 20 3 8 wide by 20 3 8 high cutout is required in the door to accommodate the grille and filter bracket Only one filter is to be used in the installation Multiple filters will r...

Page 8: ...in operating conditions frost can form on the indoor coil of an air conditioner reducing air flow and causing a lack of cooling complaint In order to prevent frost from forming the ZVAC has an automat...

Page 9: ...he room through this screened vent opening is not conditioned This unconditioned air becomes mixed with the conditioned air that is circulated by the ZVAC indoor fan This air mixture generates an addi...

Page 10: ...to raise the platform a minimum of 8 12 recommended and have a minimum load bearing capacity of 175 pounds The platform legs must be positioned so access to the unit drain connection is not blocked C...

Page 11: ...20 amp or 30 amp circuit The amount of resistance heat is determined by the selection of the correct power connection kit This is the same type of connection used by GE for years in the Premium and De...

Page 12: ...For all installations feeder sub feeder branch circuit and electrical protective devices must conform to all local codes In the absence of a local code the National Electrical Code should be followed...

Page 13: ...ger 9k 12k and 18k models only 14 RAVHW3 Hydronic kit triple row heat exchanger 12k and 18k models only 14 Unit Specifications AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC 230 208...

Page 14: ...ltage 60 Hertz 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Heating capacity designed to meet standard ARI rating conditions of 200 F water entering temp 180 F water exiting temp 70 F enter...

Page 15: ...Thermostat Heat Cool Hydronic Models 4 wire 5 wire Heat Pump Models 6 wire 6 wire Check the thermostat instructions for correct wiring and installation requirements 30 50 22 1 2 22 1 2 Cutout Dimensio...

Page 16: ...ough SIDE of case 3 min from two sides of case Plenum cutout 32 1 4 H x 20 W Drain fitting 3 4 Drain line Outside wall Platform Wall plenum Field supplied outer flashing A B A Minimum recommended acce...

Page 17: ...have a positive cooling condensate disposal system which meets the test requirements of applicable A R I standard 310 380 and 390 The disposal system shall have a slinger ring on the outdoor fan to di...

Page 18: ...dditional Specifications Service Submit complete information with bid covering service availability to whom service on units will be assigned complete address and phone number including phone number o...

Page 19: ...cessary maintenance Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Failure or damage resulting from corrosion due to installation in a...

Page 20: ...GE tradition of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2010 General Ele...

Reviews: