background image

7

geappliances.com

Permanently Lubricated Fan Motors

The ZVAC has two permanently lubricated, totally enclosed 
fan motors. The motors are permanently lubricated to reduce 
maintenance and totally enclosed to keep dirt and water out  
of the motor windings.

Standard Size Air Filter

A number of filters, providing varying degrees of filtering 
efficiency are available on the market today. GE has designed 
the ZVAC to accommodate a number of filter placement 
options. All of the options designed for the unit use a standard 
size 20" x 20" x 1" filter. Since the filter is field supplied, GE has 
allowed the owner or property manager to decide which type 
of filter to use with the unit. 
A different size filter may also be used in a field supplied frame 
installed in a return air grille mounted in the closet enclosure 
door or wall. If a different size filter is used, it must be at least  
20" x 20" x 1" and provide no more restriction to air flow than  
the standard 20" x 20" x 1" filter.
The unit must not be operated without a filter in place,  

even during construction.
GE provides three filter placement options for design and 
installation flexibility. A filter bracket is provided in the front 
panel of the ZVAC case, which allows the use of a louvered 
closet door. The bracket is mounted to allow the filter to be 
inserted from the top of the bracket rather than sliding in  
from the side, where the enclosure wall may interfere with  
filter removal. 
An access panel, accessory model number RAVRG1, for the 
closet enclosure is the second filter placement option. The 
access panel requires a 28" wide by 48" high cutout in the 
unit closet enclosure wall and provides access to the unit for 
servicing and removal. The access panel should be located in 
the wall such that the centerline of the access panel matches 
the centerline of the case to allow for removal of the chassis. The 
bottom of the access panel should be at least 1" below the unit 
support platform to allow for easy removal of the ZVAC unit.
The third filter placement option provided by GE is incorporated 
in a return air grille, accessory model number RAVRG2, 
designed to be mounted in a flat closet access door.  The 
door must have a minimum clear opening of 24" to allow for 
installation and removal of the unit. GE recommends a 28" 
wide door. A 20 3/8" wide by 20 3/8" high cutout is required in 
the door to accommodate the grille and filter bracket.
Only one filter is to be used in the installation. Multiple filters 
will reduce the air flow and affect unit performance. A clean 
filter is essential to efficient unit operation. The filter should  
be checked at least every 30 days and replaced if dirty.

Central Desk Control

Terminals are provided on the unit to allow a Central Desk 
Control system to be interfaced with the unit. The most common 
installation of this type of system is a switch mounted at the 
registration desk; and, upon guest check-in, a switch is activated 
to allow the air conditioner to operate.  
Likewise, when the guest checks out, the device is switched  
to the “OFF” setting so the unit will not operate when the room 
is not rented. In some resort areas, devices are connected to 
sliding glass doors, and opening the doors causes a contact to 
close, turning the air conditioner off. This prevents the unit from 
running and wasting energy with the sliding glass open.
Important CDC Notes:  
1) The unit requires the use of a normally open switch.   

Closing the circuit interrupts power to the unit.

2) Both wires comprising the circuit must connect to the  

CDC terminals on the unit and to the controlling switch.   

Do not use a common buss (at the unit or at the switch 

panel) in the wiring. 

3) A 24-volt transformer is contained within the ZVAC unit.   

No external voltage may be applied to the unit through 

the CDC terminals.  

4) Minimum wire size for CDC wiring:
  Wire Size # AWG  

Maximum Allowable Length

  #22 

600 Ft.

  #20 

900 Ft.

  #18 

1500 Ft.  

  #16 

2000 Ft. 

Occupancy Sensor Interface

The ZVAC is equipped with a terminal connection to allow it 
to interface with a motion sensor and a door sensor to allow 
a room occupancy detection system to be connected to the 
unit. Various companies market and install room occupancy 
systems as a means of reducing the operating cost of 
the unit. GE does not market or install these systems but 
provides the interface terminals on the unit and logic within 
the microprocessor controls to permit these systems to be 
installed at a minimum cost to the property owner. 

HIGH and LOW Fan Speeds 

If the ZVAC is connected to a wall thermostat without the ability 
to provide two fan speeds, the fan speed will be determined by 
connecting the wire controlling the fan to either the Low Speed 
Fan terminal or the High Speed Fan terminal on the unit.

Features and Benefits

Summary of Contents for Zoneline

Page 1: ...GE Zoneline vertical packaged terminal air conditioners 2010 Architects and Engineers Data Manual...

Page 2: ...cooling with electric resistance heat H heat pump with electric resistance heat W Cool only Zoneline packaged terminal unit Voltage Phase Frequency D 230 208 Volt single phase 60 Hz E 265 Volt single...

Page 3: ...rm Specifications 17 Additional Specifications 18 Warranty 19 Important Notice Equipment used as a primary source for heating or cooling is an integral part of the building in which it is installed Pr...

Page 4: ...mounted under the window there are limitations to furniture placement and curtains cannot hang to the floor Finally some people find the controls difficult to adjust for the desired temperature To ad...

Page 5: ...dehumidification Unique sleeve design for easier installation and service Three way slide out chassis service maintenance flexibility Electronic Temperature Limiting requires room air temperature sen...

Page 6: ...Temperature Limiting feature requires the use of the optional room air temperature sensor model RAVRMS Designed to be mounted on the wall of the unit enclosure closet the Room Air Temperature Sensor a...

Page 7: ...mmends a 28 wide door A 20 3 8 wide by 20 3 8 high cutout is required in the door to accommodate the grille and filter bracket Only one filter is to be used in the installation Multiple filters will r...

Page 8: ...in operating conditions frost can form on the indoor coil of an air conditioner reducing air flow and causing a lack of cooling complaint In order to prevent frost from forming the ZVAC has an automat...

Page 9: ...he room through this screened vent opening is not conditioned This unconditioned air becomes mixed with the conditioned air that is circulated by the ZVAC indoor fan This air mixture generates an addi...

Page 10: ...to raise the platform a minimum of 8 12 recommended and have a minimum load bearing capacity of 175 pounds The platform legs must be positioned so access to the unit drain connection is not blocked C...

Page 11: ...20 amp or 30 amp circuit The amount of resistance heat is determined by the selection of the correct power connection kit This is the same type of connection used by GE for years in the Premium and De...

Page 12: ...For all installations feeder sub feeder branch circuit and electrical protective devices must conform to all local codes In the absence of a local code the National Electrical Code should be followed...

Page 13: ...ger 9k 12k and 18k models only 14 RAVHW3 Hydronic kit triple row heat exchanger 12k and 18k models only 14 Unit Specifications AZ85E09DAC AZ85E12DAC AZ85E18DAC AZ85H09DAC AZ85H12DAC AZ85H18DAC 230 208...

Page 14: ...ltage 60 Hertz 230 208 230 208 230 208 230 208 230 208 230 208 230 208 Heating capacity designed to meet standard ARI rating conditions of 200 F water entering temp 180 F water exiting temp 70 F enter...

Page 15: ...Thermostat Heat Cool Hydronic Models 4 wire 5 wire Heat Pump Models 6 wire 6 wire Check the thermostat instructions for correct wiring and installation requirements 30 50 22 1 2 22 1 2 Cutout Dimensio...

Page 16: ...ough SIDE of case 3 min from two sides of case Plenum cutout 32 1 4 H x 20 W Drain fitting 3 4 Drain line Outside wall Platform Wall plenum Field supplied outer flashing A B A Minimum recommended acce...

Page 17: ...have a positive cooling condensate disposal system which meets the test requirements of applicable A R I standard 310 380 and 390 The disposal system shall have a slinger ring on the outdoor fan to di...

Page 18: ...dditional Specifications Service Submit complete information with bid covering service availability to whom service on units will be assigned complete address and phone number including phone number o...

Page 19: ...cessary maintenance Failure or damage resulting from corrosion due to installation in an environment containing corrosive chemicals Failure or damage resulting from corrosion due to installation in a...

Page 20: ...GE tradition of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2010 General Ele...

Reviews: