A-2
VersaPoint™ I/O System Profibus-DP NIU User’s Manual – August 2005
GFK-1911B
A
I/O Station Information
System Information
Number of devices per station
63, maximum
Sum of all I/O data per station
1
84 bytes, maximum
PROFIBUS-DP Interface
Copper cable (RS-485), connected via D
sub shield connector; supply electrically
isolated, shielding directly connected with
functional earth ground.
Maximum NIU current for supplying
the I/O module logic
2A at U
L
Maximum additional current for
supplying the analog terminals
0.5A at U
ANA
Maximum current consumption of
the I/O modules
See chapter 5 and the module datasheets
Observe the logic current consumption of each device when configuring a
VersaPoint station! The logic current consumption is indicated in chapter
5 and in each module data sheet. The current consumption can differ
depending on the individual module. The permissible number of devices
that can be connected depends on the specific station structure.
Maximum current carrying capacity
of the voltage jumpers U
ANA
0.5A
Maximum current carrying capacity
of the voltage jumpers U
M
, U
S
(total
current)
8A
Observe the current consumption of every device on the individual voltage
jumpers when configuring a VersaPoint station! The logic current
consumption is given in chapter 5 and in each module data sheet. The
current consumption can differ depending on the individual module. If the
maximum current carrying capacity of a voltage jumper (8A) is reached, a
new power terminal must be used.
Summary of Contents for VersaPoint IC220PB001
Page 4: ......
Page 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B ...
Page 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5 ...
Page 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6 ...
Page 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A ...