7-14
VersaPoint™ I/O System Profibus-DP NIU User’s Manual – August 2005
GFK-1911B
7
Diagnostic Update Delay
The maximum number of extra diagnostic cycles the master will wait to
obtain the release for a DATA_EXCHANGE. If the Diagnostic Update Delay
is set to 0, the master waits for one diagnostic cycle before reporting an
error. If the Diagnostic Update Delay is set to
1
5, the master waits for
1
6
diagnostic cycles before reporting an error. The master waits for one
diagnosis cycle more than the value of the Diagnostic Update Delay.
Valid range: 0 through
1
5.
Maximum Active Alarms
The maximum number of possible active alarms.
Choices:
▪
1
alarm of each type
▪
2, 4, 8,
1
2,
1
6, 24 or 32 alarms in total
Slave Functions
Extra Alarm Service Access Point
The service access point (SAP) through which the master quits alarms.
Choices:
▪
Master Alarmacknowledge SAP5
1
: Master quits alarms via SAP5
1
.
▪
Master Alarmacknowledge SAP50: Master quits alarms via SAP50.