4-10
VersaPoint™ I/O System Profibus-DP NIU User’s Manual – August 2005
GFK-1911B
4
Connecting Unshielded Cables
Unshielded cables for I/O devices and supply voltages are connected using the
spring-clamp terminals. Signals up to 250VAC/DC and 5A with a conductor cross-
section of 0.2mm
2
to
1
.5mm
2
(AWG24 –
1
6) can be connected.
For terminal assignments, please consult the appropriate module data sheet.
Follow these steps when wiring:
▪
Strip 8mm (0.3in.) off the cable. Module wiring is normally done without
ferrules. However, it is possible to use ferrules. If using ferrules, make sure
they are properly crimped.
▪
Push a screwdriver into the slot for the appropriate connection (#
1
above) so
that you can plug the wire into the spring opening.
▪
Insert the wire (#2 above). Pull the screwdriver out of the opening. The wire is
clamped.
After installation, you should label the wires and Terminal Strips as described later
in this chapter.