GFK-1911B
Chapter 6 Diagnostics
6-5
6
Error Type
(FS on, # of
FN pulses)
Error No.
(FS off, # of
FN pulses)
Meaning
Remedy
Configuration Errors on Profibus (CHK_CFG telegram)
1
Not all VersaPoint modules
that are present have been
configured.
Add extra modules to the
configuration.
2
More VersaPoint modules
have been configured than
are present.
Remove the extra modules
from your configuration or add
the missing modules.
3
The first byte of the special
identification format for the
VersaPoint module is faulty.
Determine the exact error
location, using the device-
specific diagnostics in your
control system.
4
Not enough bytes of the
special identification format
for the last VersaPoint
module have been
configured
Check the identification
format.
2
5
The sum of the configured
process data for inputs and
outputs of the VersaPoint
station is greater than
1
84
bytes.
Determine the exact error
location using the device-
specific diagnostics in your
control system.
Combine several VersaPoint
modules in the configuration,
so that the process data is
compressed (resulting in fewer
empty bits).
Summary of Contents for VersaPoint IC220PB001
Page 4: ......
Page 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B ...
Page 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5 ...
Page 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6 ...
Page 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A ...