GFK-1911B
Chapter 6 Diagnostics
6-7
6
Error Type
(FS on, # of
FN pulses)
Error No.
(FS off, # of
FN pulses)
Meaning
Remedy
Configuration Errors in the VersaPoint Station
1
The VersaPoint module
is not enabled for
operation on the NIU.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Remove the module from the
station.
2
The length code of the
VersaPoint module
corresponds to a length
of 0 bytes.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Check the module and, if
necessary, remove it from your
configuration.
3
The length code of the
VersaPoint module
corresponds to a length
of more than 32 bytes.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Remove the module from the
station.
4
Invalid module type
present in the station.
Determine the exact error location
using the device-specific
diagnostics in your control
system.
Remove the module from the
station.
5
The sum of the process
data for the local bus is
greater than 250 bytes.
Check the amount of process
data and reduce the number of
modules in the station.
6
There are more than 64
VersaPoint modules
connected.
Check whether more than 64
VersaPoint are present in the
station and reduce the number of
modules.
7
The sum of the process
data for the Profibus
inputs and outputs is
greater than
1
76 bytes
(
1
84 bytes in DP/V0
mode).
Remove the modules from the
station.
3
8
More than 8 PCP slaves
are connected.
(IC670PBI002)
Reduce the number of PCP
modules in the station
Summary of Contents for VersaPoint IC220PB001
Page 4: ......
Page 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B ...
Page 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5 ...
Page 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6 ...
Page 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A ...