8-10
VersaPoint™ I/O System Profibus-DP NIU User’s Manual – August 2005
GFK-1911B
8
Example Configuration of the VersaPoint RS-232 Module
The RS-232 Module parameters have default values. These are shown in the
example INIT-TABLE object below.
Element
Meaning
Default Setting
Data Type
Decimal
Hex
Code (hex)
Meaning
1 1
Protocol
00 Transparent
Unsigned
8
2
2
Baud rate
07
9600 baud
Unsigned 8
3
3
Data width
02
8 data bits,
even parity, 11
stop bit
Unsigned 8
4 4
Reserved
00
Unsigned
8
5 5
Reserved
00
Unsigned
8
6
6
Error pattern
24
($)
Unsigned 8
7
7
First delimiter
0D
Carriage return
(CR)
Unsigned 8
8
8
Second delimiter
0A
Line Feed (LF)
Unsigned 8
9 9 3964R
priority
00
Low Unsigned
8
10
A
Output type
00
V.24 (RS-232)
Unsigned 8
11
B
DTR control system
00
Automatic
Unsigned 8
12
C
Rotation switch
00
No rotation
Unsigned 8
13
D
XON pattern
11
Unsigned 8
14 E
XOFF
pattern
12
Unsigned
8
15-20 F-14
Reserved
00
Unsigned
8
The Profibus-DP/V1 NIU also
has o
bjects (see "Object Dictionary for the
PROFIBUS DP-V1 Bus Coupler" on page 7-12). Together, these INIT-TABLE and
the NIU objects illustrate how an intelligent slave can be accessed.
Assignment of Object Indices to the I/O Station
Slot
Index
Service
Comments
0
3
Write
Control byte (diagnostic format, manual I/O
error acknowledgement, etc)
0
4
Write
Acknowledgement of local bus event:
1: Local bus stop acknowledgement
2: I/O error acknowledgement
0
5
Read
Overview of PCP modules and status
1 to 63
2
Write
Module parameters
1 to 63
48
Read/Write
PCP data
Summary of Contents for VersaPoint IC220PB001
Page 4: ......
Page 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B ...
Page 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5 ...
Page 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6 ...
Page 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A ...