Example 1, Reading the Connected Local PCP Devices and Their Status
(Slot 0, Index 5 on the NIU)
The data shows that there is a PCP device on slot 3, and its connection status is
OK, see "Object Dictionary for the Profibus DP/V1 NIU". Byte 3 of the object data
is reserved.
Read request (master -> slave)
Data
Data Structure
5E 00 05 20
Read/Slot/Index/Maximum length
Read response (slave -> master)
Data
Data Structure
5E 00 05 03 03 01 00
Read/Slot/Index/Actual length/3 bytes of object data.