GFK-1911B
Chapter 8 Communications
8-31
8
Object Dictionary for the Profibus-DP/V1 NIU
Slot
Index
Service
Comments
1 to 63
2
Write
Module parameters
0
3
Write
Control byte (diagnostic format, manual I/O error
acknowledgement, etc)
0
4
Write
Acknowledgement of local bus event
1: Local bus stop acknowledgement
2: I/O error acknowledgement
0
5
Read/Write
Overview of PCP modules and status
0 6
Read/Write
Activate/deactivate
modules
0
7
Read/Write
Activation status of modules
0 8
Read/Write
Station
I/D
1 to 63
9
Read/Write
Module parameters (powerup)
0
10
Write
Set active configuration as powerup configuration
0
11
Write
Delete save configuration
0 to 63
47dec
Read/Write
PCP communication witth Invoke ID
1 to 63
48dec
Read/Write
PCP communication
The structure of the objects is as follows:
Index 2: Module Parameters
Index 2 can be used on some modules to change parameters during operation,
e.g., to adjust a measuring range. Changing parameters during operation is not
permitted for all modules.
Failsafe and configuration values can be specified here for each I/O module. Slot
"1 to 63" should be selected to create a reference to the I/O module. In the end it
is the NIU that makes the connection to the master and therefore index 2 is the
parameter that refers to the I/O modules, which is stored on the NIU.
Summary of Contents for VersaPoint IC220PB001
Page 4: ......
Page 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B ...
Page 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5 ...
Page 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6 ...
Page 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A ...