GFK-1911B
Chapter 4 Installation
4-19
4
Connecting Sensors and Actuators
Each module-specific data sheet indicates the appropriate Terminal Strip(s) for
that module.
Connecting Discrete Devices
VersaPoint discrete modules allow the connection of sensors and actuators in 2-
wire, 3-wire, or 4-wire technology (ability varies by module). A single Terminal
Strip can support the following connection methods:
–
2 sensors or actuators in 2-, 3-, or 4-wire technology
–
4 sensors or actuators in 2- or 3-wire technology
–
2 sensors or actuators in 2- or 3-wire technology with shielding (for analog
sensors or actuators)
The tables below summarize the connection options for 24V modules. A
connection example is given in every module-specific data sheet.
Connections for Discrete Input Modules
Connection
Abbreviation 2-Wire
3-Wire
4-Wire
Sensor signal I
N
IN
X X
X
Sensor supply U
S
/ U
M
U
S
(+24V)
X
X
X
Ground (GND)
GND
(⊥)
– X X
Ground/FE shielding
FE
–
–
X
Connections for Discrete Output Modules
Connection
Abbreviation 2-Wire
3-Wire
4-Wire
Actuator signal OUT
OUT
X
X
X
Actuator supply U
S
U
S
(+24V)
–
–
X
Ground (GND)
GND
(⊥)
X X X
Ground/FE shielding
FE
–
X
X
X Used
-- Not used
In the following figures U
S
is the supply voltage. Depending on which voltage
jumper is accessed, the main voltage U
M
or the segment voltage U
S
is the supply
voltage.
Summary of Contents for VersaPoint IC220PB001
Page 4: ......
Page 10: ...Contents x VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B ...
Page 80: ...5 14 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 5 ...
Page 100: ...6 20 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B 6 ...
Page 166: ...A 10 VersaPoint I O System Profibus DP NIU User s Manual August 2005 GFK 1911B A ...