Specifications
7-1
March 2004
General Specifications
The general specifications for the Model UTX878 flow transmitter
are divided into the following categories:
Hardware Configuration
Channel Options:
Standard:
1-Channel/Path
Optional:
2-Channel/Path (for 2-path averaging).
Enclosure:
Epoxy-coated aluminum, weatherproof, NEMA 4X, IP67
Dimensions:
Weight 3.9 lb (2 kg)
Size (h x w x d) 8.8 x 8.2 x 3.6 in. (220 x 210 x 90 mm)
Environmental
Ambient Operating Temperature:
-4° to +140°F (-20° to +60°C)
Storage Temperature:
-40° to +158°F (-20° to +70°C)
Measurement
Parameters
Volumetric flow, totalized flow, and flow velocity
Keypad
Six-button external keypad
Flow Accuracy
(% of Reading)
Pipe Diameter (ID) > 6 in. (150 mm):
±1% to 2% of reading typical
Pipe Diameter (ID) < 6 in. (150 mm):
±2% to 5% of reading typical
Note:
Accuracy depends on pipe size and whether measurement is
one-path or two-path. Accuracy to ±0.5% of reading may be
achievable with process calibration.
Range
-40 to +40 ft/s (-12.2 to +12.2 m/s)
Rangeability
400:1
Repeatability
±0.1% to 3% of reading
Note:
Specifications assume a fully developed flow profile, with a
straight run of pipe 10 diameters upstream and 5 diameters
downstream, and flow velocity greater than 1 ft/s.
Fluid Types
Acoustically conductive fluids, including most clean liquids and
many with entrained solids or gas bubbles.
Summary of Contents for UTX878 Ultrasonic
Page 2: ...iii March 2004 The UTX878 Flow Transmitter and Transducers ...
Page 8: ...Chapter 1 ...
Page 20: ...March 2004 Installation 1 11 Figure 1 5 UTX878 Outline and Installation Dwg 712 1196 rev 2 ...
Page 22: ...March 2004 Installation 1 13 Figure 1 7 UTX878 Wiring Diagram Dwg 702 528 rev 2 ...
Page 23: ...Chapter 2 ...
Page 45: ...Chapter 3 ...
Page 52: ...Chapter 4 ...
Page 60: ...Chapter 5 ...
Page 65: ...Chapter 6 ...
Page 75: ...Chapter 7 ...
Page 80: ...Appendix A ...
Page 85: ...Appendix B ...
Page 86: ...CE Mark Compliance Introduction B 1 EMC Compliance B 1 ...
Page 88: ...Appendix C ...
Page 89: ...Data Records Site Data C 1 ...
Page 93: ...Appendix D ...
Page 94: ...Service Record Introduction D 1 Data Entry D 1 Diagnostic Parameters D 3 ...