5–24
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS
CHAPTER 5: SETPOINTS
Figure 5-20: Output configuration setpoints control page continued.
Stop A
Range: N/A, C2, D1... D4 (order code dependent)
Default: N/A
This setting assigns the Stop A element to the desired contact output.
Stop B
Range: N/A, C2, D1... D4 (order code dependent)
Default: N/A
This setting assigns the Stop B element to the desired contact output.
Contactor C
Range: N/A, C2, D1... D4 (order code dependent)
Default: N/A
This setting assigns outputs of Autotransformer Starter Closed Transition and
Autotransformer Starter Opened Transition elements to the contact output wired to
contactor 2S. The selection must match the actual wiring.
NOTE
NOTE:
Stop A and Stop B are not included in the evaluation of the “Any Stop” element because
they are selective (direction/speed ). Flexlogic can be used to OR the condition for
waveform capture triggering if desired.
Communications setpoints
The MM300 has one RS485 serial communications port supporting a subset of the Modbus
protocol. An additional DeviceNet, Profibus, or Ethernet port is also available as an option.
Select the
Home > Setpnts > Cfg > Comms
page to edit the communications setpoints.
Figure 5-21: Communications setpoints page