5–52
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
PROTECTION ELEMENTS
CHAPTER 5: SETPOINTS
All RTDs programmed with an alarm or a trip are monitored for sensor failure. When the
measured temperature is greater than 250°C, the RTD is declared failed and a common
RTD open circuit alarm is issued. When the measured temperature is less than -50°C, a
common RTD short circuit/low temperature alarm is issued.
The following setpoints are available for RTD protection.
RTD Open Circuit Alarm
Range: Enabled, Disabled
Default: Disabled
Enable to generate an alarm if RTD is open circuit.
RTD Open/Short Circuit Alarm
Range: Enabled, Disabled
Default: Disabled
Enable to generate an alarm if RTD is shorted/opened.
RTD #1 Application to RTD #3 Application
Range: None, Stator, Bearing, Ambient, Other
Default: None
These setpoints select the application type for RTDs #1 through 6, respectively.
RTD #1 Alarm Temp to RTD #6 Alarm Temp
Range: 1 to 250°C in steps of 1 or OFF
Default: OFF
These setpoints specify the alarm temperature for RTDs #1 through 6, respectively.
20
68
107.79
30
86
111.67
40
104
115.54
50
122
119.39
60
140
123.24
70
158
127.07
80
176
130.89
90
194
134.70
100
212
138.50
110
230
142.29
120
248
146.06
130
266
149.82
140
284
153.58
150
302
157.32
160
320
161.04
170
338
164.76
180
356
168.47
190
374
172.46
200
392
175.84
210
410
179.51
220
428
183.17
230
446
186.82
240
464
190.45
250
482
194.08
Temperature
Resistance (in ohms)
°C
°F
100 Pt