5–28
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS
CHAPTER 5: SETPOINTS
Reset TCU Using Reset key
Range: Disabled/Enabled
Default: Enabled
If set to "Enabled", when a Lockout Reset is used to reset a Thermal Overload, the
Thermal Capacity % will be reset to zero.
Note that the RESET button of the GCP and BCP can be used to send a
'Lockout Reset
command'
or a
'Thermal Capacity Reset'
command. If the RESET button is pressed for
less than 10 seconds, a
'Lockout Reset'
or
'Non-Lockout Reset'
is sent. However, by
pressing the RESET button for more than 10 seconds, a
'Reset Thermal Capacity'
command is sent.
NOTE
NOTE:
When a GCP/BCP reset key is pressed continuously for longer than 12 seconds the
Thermal Capacity % will be reset to zero, independently of the Reset TCU Using Reset Key
setting configuration.
Change Mode When Running
Range: Disabled/Enabled
Default: Enabled
If set to "Enabled," the Auto/Manual mode can be changed while the motor is running.
Set Date
Set to program today’s date.
Set Time
Set to program current time.
Time Offset from UTC
Range: -24 to +24 step 0.25
Default: 0.00
Enter the time in hours that your zone is off from Universal Time.
Daylight Savings
Range: Disabled/Enabled
Default: Disabled
Set to enable automatic time change based on the DS time setpoints.
NOTE
NOTE:
Once this setting is
enabled
all the Daylight Savings (DST) settings need to be configured to
valid values and not left in the "Not Set" state.
Orange LED Intensity
Range: 1 to 6
Default: 1
Selects brightness level (1 to 6) for Control Panel LEDs.
Green LED Intensity
Range: 1 to 6
Default: 1
Selects brightness level (1 to 6) for Control Panel LEDs.
Red LED Intensity
Range: 1 to 6
Default: 1
Selects brightness level (1 to 6) for Control Panel LEDs.