5–32
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
CONFIGURATION SETPOINTS
CHAPTER 5: SETPOINTS
Sample Rate
Range: 1 cycle, 1 second, 1 minute, 1 hour
Default: 1 second
Determines how often data is stored in the data log.
Continuous Mode
Range: Disabled, Enabled
Default: Disabled
Determines whether or not the trigger data is overwritten with new data. Enabled will
overwrite the previous trigger data with new trigger data. When Disabled, the data log
will run until filled with 256 samples. Continuous Mode should be used when the data is
stored externally by a polling system. The sample rate should be chosen to match the
poll rate of the external program.
Trigger Position
Range: 0 to 100% steps of 1%
Default: 25%
Percentage of the sample buffer used for pretrigger samples.
Trigger Source
Range: Command, VO1 to VO32, Any Trip Pickup, Any Trip, Any Trip Dropout, Any Alarm
Pickup, Any Alarm, Any Alarm Dropout, Any Stop, Start A, Start B
Default: Command
Selects a trigger source. Command is always active. Flexlogic can be used to create
combinations of trigger sources.
Channel 1 Source
Range: Disabled, Phase A Current, Phase B Current, Phase C Current, Average Phase
Current, Motor Load, Current Unbalance, Ground Current, System Frequency, Vab, Vbc,
Vca, Van, Vbn, Vcn, Power Factor, Real Power (kW), Reactive Power (kvar), Apparent Power
(kVA), Positive Watthours, Positive Varhours, Hottest Stator RTD, Thermal Capacity Used,
RTD #1, RTD #2, RTD #3, RTD #4, RTD #5, RTD #6
Default: Disabled
Selects the data to be stored for each sample of the data log channel.
NOTE
NOTE:
Sources and Defaults for Channels 2 to 10 are the same as those for Channel 1.
Counters
Figure 5-26: Counters setpoint page
The following setpoints are available:
Summary of Contents for Multilin MM300
Page 20: ...1 14 MM300 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Page 184: ...6 8 MM300 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL COMMANDS CHAPTER 6 DIAGNOSTICS ...
Page 198: ...A 6 MM300 MOTOR MANAGEMENT SYSTEM INSTRUCTION MANUAL REPAIRS CHAPTER A APPENDIX A ...