5–66
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
SYSTEM SECURITY
CHAPTER 5: SETPOINTS
Passcode Level 1, Passcode Level 2, Passcode Level 3
Range: any five-digit number using digits 1 through 5 only or Disabled
Default value: 11111 (level 1), 22222 (level 2)
Access is granted if a passcode has been correctly entered matching the value of this
setpoint.
Access Switch Level
Range: 1, 2, 3
Default value: 1
Sets the access level provided by the access switch being closed. The contact input for
the access switch is configured on the contact inputs page.
Comms security
Range: Enabled, Disabled
Default: Disabled
Sets whether the security feature applies to the communications ports.
MCC setpoint access
Range: Enabled, Disabled
Default: Enabled
Sets whether the setpoint access is allowed from the control panel display.