3–42
MM300 MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL
SOFTWARE
CHAPTER 3: INTERFACING WITH THE MM300
Data logger
The data logger feature is used to sample and record up to ten actual values at a
selectable interval. The datalogger can be run with Continuous mode Enabled, which will
continuously record samples until stopped by the user; or with Continuous mode Disabled,
which will trigger the datalog once without overwriting previous data.
Viewing and saving of the Datalogger is performed as follows:
1.
With EnerVista MM300 Setup running and communications established, select the
Diagnostics > Datalog
menu item to open the datalog setup window:
2.
If Continuous mode is enabled, click on
Stop
to stop the datalog
3.
Click on the
Save to File
button to save the datalog to the local PC. A new window will
appear requesting for file name and path.
4.
One file is saved as a COMTRADE file, with the extension ‘CFG’. The other file is a DAT
file, required by the COMTRADE file for proper display of data.
5.
To view a previously saved COMTRADE file, click the
Open
button and select the
corresponding COMTRADE file.
6.
To view the datalog, click the
Launch Viewer
button. A detailed Datalog window will
appear as shown below.
Setting
Parameter
Sample Rate
1 Second
Continuous Mode
Disabled
Data Log Trigger Position
25%
Data Log Trigger Source
None
Channel 1 Source
Phase A Current
Channel 2 Source
Phase B Current
Channel 3 Source
Phase C Current
Channel 4 Source
Disabled
Channel 5 Source
Disabled
Channel 6 Source
Disabled
Channel 7 Source
Disabled
Channel 8 Source
Disabled
Channel 9 Source
Disabled
Channel 10 Source
Disabled