PRODUCT DESCRIPTION
GEK-106273L
MIF Digital Feeder Protection
6-41
6.2
OUTPUTS AND LEDS CONFIGURATION (ONLY FOR OPTION 1 AND OPTION 2
MODELS)
6.2.1.
DESCRIPTION OF OUTPUTS AND LEDS
The MIF incorporates 4 configurable outputs and 4 LED indicators, which can only be configured by ENERVISTA MII
SETUP software.
The default configuration for outputs is as follows:
OUTPUT CONFIGURATION MEMORY
1 Phase
trip No
2 Ground
trip No
3 50
Trip No
4 49
Alarm No
The default LED configuration is as follows:
LED CONFIGURATION
MEMORY
1 Phase
trip Yes
2 Ground
trip Yes
3 50
Trip Yes
4 Pickup No
Functions that can be assigned to Outputs/LEDs are divided in eight groups, besides the
No definition
function.
Functions belonging to the same group can be assigned to the same output/LED. Functions of different groups need
to be assigned to different outputs/LEDs.
In order to assign several functions to an output/LED, first we must activate the
OR
button, click on the
I/O
CONFIGURATION
frame and select the desired group, then select the desired functions. In order to negate a
function, select the
NOT
button. Finally, click on the
OK
button.
Now you can invert all the logic by selecting the general NOT button. Outputs can be memorised, and LEDs can be
set to be fixed or blinking.
If we want to assign a phase trip to an output or LED, we must program the output or LED with 50PH pickup, 50PL
pickup and 51P functions.
If we want an output or LED to be active when function is Remote, we must program the output or LED with the
Local/Remote function inverted with NOT.
50PH trip
50PL trip
51P trip
Output/LE
Output/L
Local/Remo
Summary of Contents for GEK-106273L
Page 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Page 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Page 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Page 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Page 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Page 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...