ANNEX 3 MODBUS MEMORY MAP
GEK-106273L
MIF Digital Feeder Protection
13-1
13. ANNEX 3. MODBUS
®
MEMORY MAP
This annex describes the fundamentals about the communication with MIF units using ModBus
®
protocol. The
references to memory addresses can vary depending on the model, or between different firmware versions; for this
reason, you must make sure that you have the appropriate memory map for your MIF model and firmware version.
To make this easy, the ENERVISTA MII SETUP software supplied with M Family units incorporates, in versions 1.8
and higher, a tool that allows to extract the memory map of any M Family unit (MIF, MIV, MIG, MIN, MIW, etc.)
connected to the PC.
13.1
READING VALUES
The MODBUS
®
function used in this case is number 3 (READ HOLDING REGISTERS). The message request
command is generated as follows:
Request:
FIELD LENGTH
Relay address
1 Byte
Function
1 Byte (03H)
Beginning address
1 word (High Byte– Low Byte)
Nº records
1 word (High Byte– Low Byte)
CRC
1 word
Reply:
FIELD LENGTH
Relay address
1 Byte
Function 1
Byte
No. of bytes
1 Byte
Value of the records
No. of bytes/2 words
CRC
1 word
Example:
Request:
Reading of 75 records (150 bytes) beginning from address 04FE (1278).
ADDRESS FUNCTION
BEGINNING #REGS CRC
01 03
04FE
004B
653D
Reply:
ADDRESS FUNCTION BYTES
DATA0
...
DATA74
CRC
01 03
96
500D
0200
84 D5
Summary of Contents for GEK-106273L
Page 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Page 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Page 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Page 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Page 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Page 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...