PRODUCT DESCRIPTION
GEK-106273L
MIF Digital Feeder Protection
3-33
In the basic model, outputs are configured as follows:
OUT1: Phase Trip
OUT2: Ground Trip
OUT3: 50 Trip
OUT4: 49 Alarm
Each output has a different configuration, and it is able to operate independently to the others.
If Jx jumper is removed, the output contact configuration change as shown in the following figure:
After removing the Jx Jumper, the outputs are divided in two groups: Independent and isolated.
Group1:
Output 1: Terminals B8-B7
Group 2:
Output 2: Terminals B9-A7
Output 3: Terminals B10-A7