PRODUCT DESCRIPTION
GEK-106273L
MIF Digital Feeder Protection
3-29
3.2.3.
AC CURRENT TRANSFORMER INPUTS
Each AC current input has an isolating transformer and an automatic mechanism that shorts the input when the
module is withdrawn from the chassis. There are no internal ground connections on the current inputs. Current
transformers with 1 A or 5 A rated secondary current may be used.
CAUTION: VERIFY THAT YOUR RELAY MODEL CORRESPONDS TO YOUR RATED SECONDARY CURRENT.
UNMATCHED CTS MAY RESULT IN EQUIPMENT CMAGE OR INADEQUETE PROTECTION.
The exact placement of a zero sequence CT, so that ground fault current will be detected, is shown below. Twisted
pair cabling on the zero sequence CT is recommended.
Figure 3-6 ZERO SEQUENCE CORE BALANCE CT INSTALLATION
UNSHIELDED CABLE
LOAD
GROUND CONNECTION TO NEUTRAL
MUST BE ON SOURCE SIDE.
GROUND
OUTSIDE CT
SOURCE
SHIELDED CABLE
LOAD
SOURCE
STRESS CONE
SHIELDS
GROUND CONNECTION
MUST BE ON LOAD SIDE